Siemens FT2010 Operation Manual Download Page 21

Operation

Switch off alarm delay

6

21 | 40

Building Technologies

009310_l_en_--

Fire Safety

2018-08-29

6.2 Switch off alarm delay

An alarm delay in case of alarm is only possible if the fire detection installation is

provided with ↑ 'AVC'. Alarm delay is a countdown until global alarming is initiated.
In case of alarm, the alarm delay can be switched off. Global alarming is triggered

immediately!

Switching off the alarm delay

κ

Press <Alarm delay off>.

Global alarming is activated immediately.

6.3 Resetting an alarm

The alarm message must be acknowledged before 'ALARM' 'Reset'.
In order to 'ALARM'-'Reset', the 'Key switch' must be moved into its horizontal

position.
If the cause of an 'ALARM' is not remedied, a new alarm event will be triggered

after 'ALARM' Reset'.

↑ Person Machine Interface with R button ('Reset')

'ALARM' 'Reset'

1. Turn the 'Key switch' into a horizontal position.

Operation is released.

2. Acknowledge the alarm message.
3. Press <R>.

'ALARM' is reset.

The ↑ floor repeater terminal is in quiescent condition if there are no other

messages.

R

Summary of Contents for FT2010

Page 1: ...FT2010 Floor repeater terminal Operation Manual MP7 IP7 009310_l_en_ Building Technologies 2018 08 29 Control Products and Systems ...

Page 2: ...nication thereof to others without express authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Theilerstrasse 1a CH 6300 Zug Tel 41 58 724 2424 www siemens com buildingtechnologi...

Page 3: ... that can be displayed 14 4 PMI 15 4 1 Buttons on the PMI 16 4 2 Display 16 4 3 Key switch 17 4 4 LEDs 17 5 Service menu 18 6 Operation 19 6 1 ALARM Procedure 19 6 2 Switch off alarm delay 21 6 3 Resetting an alarm 21 6 4 Procedure in case of Fault 22 6 5 Switching an object on off 23 6 6 Testing indicators 24 6 7 Indicating and scrolling in lists 24 6 7 1 Show ALARM list 24 6 7 2 Indicating fault...

Page 4: ...Building Technologies 009310_l_en_ Fire Safety 2018 08 29 4 40 8 Faults Troubleshooting 34 9 Maintenance 35 Glossary 36 Index 38 ...

Page 5: ... of these duties can be delegated to others as required For large or complex electrical installations or networks the duties can be delegated for parts of the installations or the network Commissioning personnel Configures the product at the place of installation according to customer specific requirements Checks the product operability and releases the product for use by the operator Searches for...

Page 6: ... shown in this document as follows Requirement for a behavior instruction 1 2 Behavior instruction with at least two operation sequences Version option or detailed information for a behavior instruction Intermediate result of a behavior instruction End result of a behavior instruction Numbered lists and behavior instructions with an operation sequence X Reference to a page number Text Quotation re...

Page 7: ..._________________________________ __ ABCD 026 ABC 75 ABCDE CCC XXX YYY ZZZ 3 __________________________________ __ XXX YYY ZZZ 2 Table 1 Display representation in tables The table representation has the following key deviations from the original Font and representation proportional font not inverted No frame around selection 1 2 Applicable documents Sinteso document ID Title 008838 FC20xx FT2040 o...

Page 8: ...rst edition of a language version or a country variant may for example be version d instead of a if the reference document is already this version Version Edition date Brief description l 2018 08 29 Edition for MP7 IP7 k 2015 12 15 Edition for MP6 IP6 Referenced documents updated j 2014 01 28 Chapter LEDs revised i 2013 11 14 Edition for MP5 IP5 h 2013 05 20 Change to date format according to ISO ...

Page 9: ...bols These symbols indicate general dangers the type of danger or possible consequences measures and prohibitions examples of which are shown in the following table General danger Explosive atmosphere Voltage electric shock Laser light Battery Heat Signal word The signal word classifies the danger as defined in the following table Danger level DANGER identifies a dangerous situation which will res...

Page 10: ...ations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards Should additional national or local safety standards or legislation concerning the planning mounting installation operation or disposal of the product apply at the place of operation then these must also be taken into account together with the safety regula...

Page 11: ...he remote transmission from triggering erroneously If testing building installations or activating devices from third you must collaborate with the people appointed The activation of fire control installations for test purposes must not cause injury to anyone or damage to the building installations The following instructions must be observed Use the correct potential for activation this is general...

Page 12: ...sregard of danger warnings contained in the documentation This applies in particular to the following damage Personal injuries or damage to property caused by improper use and incorrect application Personal injuries or damage to property caused by disregarding safety instructions in the documentation or on the product Personal injury or damage to property caused by poor maintenance or lack of main...

Page 13: ... before you plan and or configure a fire detection installation Read the Release Notes before you carry out a firmware update to a fire detection installation NOTICE Incorrect planning and or configuration Important standards and specifications are not satisfied Fire detection installation is not accepted for commissioning Additional expense resulting from necessary new planning and or configurati...

Page 14: ...lity and shows the same event texts The possible number of displayed events is limited You will find details in the corresponding section 3 1 Maximum number of events that can be displayed The maximum number of events that can be displayed is limited and depends on the length of the event texts Assuming that the event texts are long the following maximum numbers of events apply to the correspondin...

Page 15: ...w shows the PMI of the floor repeater terminal Figure 2 PMI of the floor repeater terminal 1 ALARM LEDs 7 More alarms button 2 Display 8 LED System On 3 Navigation buttons 9 LED Remote alarm Active 4 Silence buzzer button K LEDs and function keys configurable 5 Acknowledge button S Key switch 6 Reset button 1 2 3 6 7 8 9 5 4 S K K K K K K ...

Page 16: ...ton the display changes to the next alarm event In case of alarm this button has the same function as the navigation button Configurable buttons These configurable buttons may for example be assigned with the following functions Alarm delay off Switches off the alarm delay for all Events In the event of an alarm the remote transmission or global alarming respectively is activated immediately Fault...

Page 17: ...port the operator s orientation The LEDs can light up in red yellow or green The LEDs can be configured according to customer specific requirements The LED colors can for example signal the following information Red ALARM Activations e g remote transmission alarm devices control function Yellow Fault Isolation Deactivation e g remote transmission alarm devices control function Green System is in o...

Page 18: ...r calling up the menu and entering a password the following menu items are available Device information Shows detailed information on the device Buzzer on off Settings of the buzzer LED test Function test of the LED Key test Function test for the buttons of the PMI LCD test Function test of the display LCD contrast Setting of the display contrast in percent exit Closes the service menu See also 1 ...

Page 19: ...rm transmission function AVC the variant Fire Brigade in mm ss in Step 2 see Procedure in the event of alarm does not apply Figure 4 ALARM operation sequence 1 Acknowledge 3 Indication of the fire location on the display 2 Top line on the display R Reset The Alarm delay off button is not indicated as the command can be assigned to each of the configurable buttons R 1 2 3 ...

Page 20: ...n available Fire brigade must be called by phone No automatic transmission to fire brigade 3 Read off fire location on display 4 Go to the fire location 5 Decide MAJOR INCIDENT or minor incident Condition MAJOR INCIDENT Minor incident Fire brigade has been called Save people Guide the fire brigade to the fire location Fight the fire Try to prevent fire brigade deployment Press Reset Fire Brigade i...

Page 21: ...alarm delay κ Press Alarm delay off Global alarming is activated immediately 6 3 Resetting an alarm The alarm message must be acknowledged before ALARM Reset In order to ALARM Reset the Key switch must be moved into its horizontal position If the cause of an ALARM is not remedied a new alarm event will be triggered after ALARM Reset Person Machine Interface with R button Reset ALARM Reset 1 Turn t...

Page 22: ...f Intervention Concept events of the Fault category can be assigned their own sequence This sequence may be configured differently and depends on the Manned operation Unmanned operation operation mode An exemplary sequence after a Fault on consideration of the Intervention Concept is graphically represented in the following Fault has occurred Unmanned operation operation mode Remote transmission f...

Page 23: ...on OFF button to switch off a pre the touch of a button WARNING System parts that have been switched off make it impossible to acquire and process alarms or faults Fire may spread unhindered Deploy staff to monitor the deactivated area You must switch deactivated parts of the Site back on as soon as possible If a deactivated Zone is the only Zone in a Section the indicated as deactivated Switching...

Page 24: ...l s configured visibility are indicated in lists If a list contains several Events you may scroll to the next list item by means of the navigation buttons The next Event is highlighted When the ALARM event list is open the More alarms button assumes the function of the button changing to the next alarm event upon activation See also 1 Maximum number of events that can be displayed 14 6 7 1 Show AL...

Page 25: ...or an ALARM the most important Event or the most important condition respectively is indicated on the display Indication of the fault list ϖ A button is configured with the Show Fault function ϖ The button is labelled accordingly κ Press Show Fault The fault list is indicated on the display Example for a fault list with two Faults 002 Faults Device missing Office Room 123 Dev location fault Corrid...

Page 26: ...y Displaying the Pre ALARMS list ϖ A button is configured with the Show Pre ALARMS function ϖ The button is labelled accordingly κ Press Show Pre ALARMS All Pre ALARMS which have occurred within the configured visibility are indicated on the display Example for PRE ALARM list 001 PRE ALARM PRE ALARM Office 22 Zone 2 4 List with PRE ALARM in Zone 2 4 See also 1 Maximum number of events that can be ...

Page 27: ...lations list ϖ A button is configured with the Show Isolations function ϖ The button is labelled accordingly κ Press Show Isolations All Isolations within the configured visibility are indicated on the display Example for Isolations list 003 Isolations OFF Office 22 OFF MCP Corridor 2nd floor Zone Zone 2 4 2 1 Indication of list with two of three Isolations See also 1 Maximum number of events that...

Page 28: ...ssages TECHNICAL Ventilation flap Office 22 TECHNICAL Valve Corridor 3rd floor Zone Zone 2 4 2 1 Display of the list with 2 of 5 Technical messages See also 1 Maximum number of events that can be displayed 14 6 8 Open service menu Select menu item To open the service menu a keyboard shortcut as well as a password are required The service menu can only be opened when no Event is displayed Opening t...

Page 29: ...lse alarm or minor incident the intervention of the fire brigade can be avoided Information flow of ALARM and Pre ALARM D Detection tree AL Pre ALARM ALARM AVC Alarm verification concept GS Danger levels 1 Area The Area receives Pre ALARMS or ALARMS from Zones Alarm verification takes place at Area level Configuration for Pre ALARMS and ALARMS is not related within AVC The type of verification and...

Page 30: ...ming is then triggered In the case of a minor incident or false alarm the operator may reset the ALARM and cancel alarming If the ALARM is not reset within the given time t2 Immediate global alarming is activated 7 3 Example of a verification process Alarm verification proceeds as follows An alarm event activates local alarming and starts the time t1 for attendance check Operating personnel acknow...

Page 31: ...ication 1 Alarm event q Acknowledge at Station 2 Local alarming qx Not acknowledged 3 Manual call point or Alarm delay off on Station t2 Time t2 to investigate the source of alarm the fire location mx Unmanned operation operation mode t2 X Time t2 has expired m Manned operation operation mode r Reset on Station t1 Time t1 for attendance check rx Not reset t1 X Time t1 has expired GA Global alarmin...

Page 32: ... the alarm devices can be configured differently for local and global alarming the alarm devices must be suitable for this Remote transmission The alarm message is transmitted to an intervention station In the case of local alarming this is usually the company fire brigade and for global alarm usually the state fire brigade A remote transmission device must be used to transmit alarm messages via t...

Page 33: ... devices and the remote transmission can be separately configured for Alarm type only with automatic zones Pre ALARM ALARM Zone type only with ALARMS Manual alarm Automatic alarm Degraded fire alarm Operation mode Manned operation Unmanned operation Alarming type Local alarming only Delayed alarming Global alarming only ...

Page 34: ...nsert Detector Detector defective Replace Detector with replacement detector CAUTION Any defective Detector must always be replaced by a Detector of the same type Manual call point Glass pane broken Replace glass pane Other damages Contact service provider Mains failure Mains failure in the public network No action required Emergency power supply is ensured by batteries during at minimum 12 hours ...

Page 35: ...echnologies 009310_l_en_ Fire Safety 2018 08 29 9 Maintenance Please adhere to the local provisions No maintenance work is required Cleaning the PMI To clean the PMI use a wet cloth without any cleaning agents abrasives or solvents ...

Page 36: ...ger 2 probable danger 3 highly probable danger Detection tree Diagram of the geographical and organizational arrangements of sensors in a building This is a hierarchical structure comprising the area section and zone False alarm Alarm not triggered by a danger Floor repeater terminal A display device with operating elements for acknowledging and resetting alarms and faults Global alarming Global a...

Page 37: ...mation early on should an event occur Remote transmission Remote transmission Section Level in detection tree of the fire detection system The section is assigned to the area It is used for combining zones Site Depiction of fire detection installation The top level in the figure showing the installed system Combines hardware tree detection tree and control tree Technical message Events e g from th...

Page 38: ...ire Safety 2018 08 29 Index A Alarm verification concept AVC 29 Example of verification process 30 AVC Alarm verification concept 29 Example of verification process 30 D Download center URL 8 L LEDs Colors 17 O Original language 5 S Source language 5 ...

Page 39: ...Index 39 40 Building Technologies 009310_l_en_ Fire Safety 2018 08 29 ...

Page 40: ...rnational Headquarters Theilerstrasse 1a CH 6300 Zug 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2006 Technical specifications and availability subject to change without notice Document ID 009310_l_en_ Manual FS20 FS720 Edition 2018 08 29 ...

Reviews: