Ethernet switch (modular) FN2012-A1
Description
1
6 | 34
Building Technologies
A6V10407862_d_en_--
Siemens Industry, Inc.
2018-09-07
Properties
● Can be installed in approved FS20/FS920 housing
● Can be installed in approved XLS housing
● 2x Ethernet ports for local Ethernet (panel-internal)
● 2x Ethernet ports for external Ethernet (increased EMC safety and ground fault
supervision)
● MoNet bus connection for transmitting signals from the peripheral data bus and
SAFEDLINK degraded mode signals via the connection module (MoNet)
● Configurable via a 16-pin rotary switch
● 1x dry contact relay output for fault signals
● Transmission of degraded mode signals from the system and the FCnet/C-WEB
network should the main CPU fail
● Several supply options
– Via the supply connection (redundant)
– Via PoE with optional Ethernet module (electric)
– Via MoNet bus
● 2x slots for optional Ethernet modules (ring ports) – not included in scope of supply
– VN2001 Ethernet module (electric) for distances up to 330 ft/100 m
– VN2002 Ethernet module (MM), optical Ethernet module for distances up to
13123 ft/4 km with an 11 dBm loss
1
– VN2003 Ethernet module (SM), optical Ethernet module for distances up to
131233 ft/40 km with a 29 dBm loss
1
1
The length is a guide value dependent upon the loss of the optical cable