background image

Wiring
Ethernet switch as a repeater

4

22 | 34
Building Technologies

A6V10407862_d_en_--

Siemens Industry, Inc.

2018-09-07

Two repeaters

Figure 15: 2x Ethernet switch (modular) as a repeater in the electric Ethernet

Jumper settings on the VN2001 with two repeaters:

Switch/repeater

VN2001 in port P1

VN2001 in port P0

Switch 1

Not connected

PoE

Repeater 1

PoE

Ground fault supervision

Repeater 2

Neutral position

PoE

Switch 2

PoE

Not connected

Guidelines

● Max. two repeaters between two nodes.
● Electric Ethernet distance between two nodes maximum 300 ft/100 m.
● Repeater power supply via 'Power over Ethernet' (PoE) from the VN2001.
● For each switch (node), 1 repeater can be supplied with power.
● The switch carries out ground fault supervision as far as the repeater.
● If there are two repeaters, the first one transfers ground fault supervision to the

second repeater.

MoNet

PMI & Mainboard

Ethernet

P2

P3

P4

P5

P0

P1

P

O

W

E

R

FA

U

LT

MoNet

Panel

P2

P3

P4

P5

P0

P1

P

O

W

E

R

F

A

U

LT

MoNet

P2

P3

P4

P5

P0

P1

P

O

W

E

R

F

A

U

LT

MoNet

MoNet

PMI & Mainboard

Ethernet

P2

P3

P4

P5

P0

P1

P

O

W

E

R

F

A

U

LT

MoNet

Panel

Electrical Ethernet

Repeater1

Repeater2

Switch1

Switch2

100 m

100 m

100 m

Ground fault

PoE & Ground fault

PoE

P1

P0

P1

P0

P1

P0

P1

P0

Summary of Contents for FN2012-A1

Page 1: ...FN2012 A1 Ethernet Switch modular Mounting Installation For UL portfolio A6V10407862_d_en_ Building Technologies 2018 09 07 Siemens Industry Inc ...

Page 2: ...on of its contents and communication thereof to others without express authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Industry Inc Building Technologies Division 8 Fernwood Road Florham Park NJ 07932 Tel 1 973 593 2600 www sbt siemens com FIS Edit...

Page 3: ...nstallation of the Ethernet modules 10 3 Views 12 4 Wiring 14 4 1 Wiring overview 14 4 2 General wiring FS20 FS920 16 4 3 General wiring XLS 17 4 4 MoNet bus connection 18 4 5 Ethernet switch in the Ethernet network 19 4 6 Ethernet switch as a repeater 21 5 Jumper settings on the VN2001 23 6 Pin assignments 25 6 1 POWER connector strip 25 6 2 FAULT connector strip 26 7 Indicators 27 8 Adjustment e...

Page 4: ...Building Technologies A6V10407862_d_en_ Siemens Industry Inc 2018 09 07 4 34 ...

Page 5: ...ernet and an extension to the ground fault supervision for the electric Ethernet It also supports the physical connection to voice and VoIP components The Ethernet switch has two slots for optional Ethernet modules Depending on the application the Ethernet switch is supplied via a 24 V input via PoE using the Ethernet module electric or via the connection module MoNet FCA2031 Intended use Integrat...

Page 6: ... 16 pin rotary switch 1x dry contact relay output for fault signals Transmission of degraded mode signals from the system and the FCnet C WEB network should the main CPU fail Several supply options Via the supply connection redundant Via PoE with optional Ethernet module electric Via MoNet bus 2x slots for optional Ethernet modules ring ports not included in scope of supply VN2001 Ethernet module ...

Page 7: ...20 housing The Ethernet switch modular FN2012 can be installed in all FS20 FS920 housings 1HU and 2HU The example below illustrates installation in a fire control panel in the housing 2HU If the Ethernet switch modular is used as a repeater it is installed as a separate component in an external housing 1HU Figure 1 Installing the Ethernet switch modular in housings 2HU ...

Page 8: ...lar with Ethernet modules installed 3 3x fixing screw 4 Fixing slot in side tab 5 Threaded standoffs on back box 1 Position the Ethernet switch 2 as shown 2 Inserting the 3 fastening screws 3 into the side tabs 4 and screw the Ethernet switch 2 to the threaded sleeves 5 in the back box 1 3 Wire up the Ethernet switch according to the wiring information provided below ...

Page 9: ...gs 1 Housing back box 2 Ethernet switch modular with Ethernet modules installed 3 3x fixing screw 4 Fixing slot in side tab 5 Threaded standoffs on back box 1 Position the Ethernet switch 2 as shown 2 Inserting the 3 fastening screws 3 into the side tabs 4 and screw the Ethernet switch 2 to the threaded sleeves 5 in the back box 1 3 Wire up the Ethernet switch according to the wiring information p...

Page 10: ...ion All Ethernet modules are installed in the same way Figure 3 Installing the Ethernet module in the FN2012 1 Ethernet switch modular FN2012 2 Ethernet module installed 3 Fastening screw with retention spring 4 Ethernet module 5 Plug contacts 6 Threaded hole for fastening 7 Positioning aid Before the Ethernet module electric VN2001 is installed the jumper settings must be plugged in as appropriat...

Page 11: ... module 4 into the opening of the option slot so that the plug contacts 5 slot into the Ethernet switch plug connector 3 Make sure that the Ethernet module 4 slots into the positioning aids 7 4 Use the fastening screw 3 to fix the Ethernet module in the threaded hole 6 5 Wire up the Ethernet module according to the wiring information provided below See also 1 Jumper settings on the VN2001 23 ...

Page 12: ...onnector strip for fault signals F1 F2 dry contact relay for fault output F3 F4 not connected MoNetBus Knock out sheet cover on the X201 connector strip for the MoNet bus flat cable LEDs RM Redundancy manager indicator redundancy master FAULT General fault PWR Normal operation hardware ready for operation PD Not connected Switches and keys CONFIG S302 rotary switch with 16 positions for pre config...

Page 13: ...rnal Ethernet connection 1 FIELD limited to the same housing or the same room up to a maximum length of 20 ft 6 m P2 External Ethernet connection 2 FIELD limited to the same housing or the same room up to a maximum length of 20 ft 6 m Figure 6 View of option slots not in use FN2012 Key for the option slots Element Des Function Connector P0 RING port 0 socket X1 for the optional Ethernet module opt...

Page 14: ...witch built into an FS20 panel as well as all connections The example shows the wiring of a panel in an optical Ethernet ring Figure 7 Wiring of the Ethernet switch modular FN2012 All of the connections shown are current limited and supervised P5 P4 P3 P2 P0 P1 POWER FAULT MoNet Ethernet Ring MoNet PMI Mainboard Ethernet FCA2031 Panel 2x Ethernet internal 2x Ethernet external MoNetBus X ...

Page 15: ...S Desigo Fire Safety View MoNet Connection from the PMI mainboard to the Ethernet switch modular for the supply and transmission of the degraded mode and system signals MoNetBus FCA2031 Connection module MoNet in the slot on the SAFEDLINK main module Makes the MoNet bus available X Not used Panel Approved Siemens panel in which the Ethernet switch modular is being installed The electrical Ethernet...

Page 16: ...0 Figure 8 View of cable routing Supply and battery connection The wiring must be routed as far away as possible from the installed components and the non current limited cables and fixed in place appropriately Cable guides in the housing Current limited and non current limited cables must not be routed together through the same cable entry ...

Page 17: ...S Figure 9 Wiring overview of XLS components The Ethernet switch modular is supplied via the PSC 12 power supply connection TB4 The internal Ethernet connection is established between port 4 or port 5 on the Ethernet switch modular and the PMI 2 connection J11 J11 P4 P5 local Ethernet TB4 non power limited DC 24 V OUT POWER A A ...

Page 18: ...ate κ Use a screwdriver to carefully remove the cover plate for the MoNet connector as shown in the illustration Levering the screwdriver in the direction shown by the arrow causes the cover plate to come loose at the four predetermined breaking points Ribbon cable connection for MoNet bus Figure 11 Connecting the MoNet bus ribbon cable κ Connect the 1 35 m 4 43 ft long ribbon cable for the MoNet ...

Page 19: ...nection in single mode version with a VN2003 module max 131000 ft 40 km long The type of ring wiring between each switch is independent and can be selected at will A maximum of 32 switches are allowed for each Ethernet ring The switch built into an FS20 panel is supplied via the MoNetBus from the PMI mainboard If the switch is built into another housing or device it is supplied with power via a 24...

Page 20: ...rvision 3 open Ground fault supervision 4 open Ground fault supervision 5 open Ground fault supervision The minimum cable length for an electrical 10 100BaseT cable on the VN2001 is 10 ft 3 m Shorter lengths are only permitted within the same housing or if the connection does not need to be supervised in accordance with the UL864 standard Switch1 P2 P3 P4 P5 P0 P1 POWER FAULT MoNet Switch2 P2 P3 P...

Page 21: ...module electric The settings for PoE and ground fault supervision are made by plugging jumpers into slots P0 and P1 on the corresponding Ethernet module electric One repeater Figure 14 1x Ethernet switch modular as a repeater in the electric Ethernet Jumper settings on the VN2001 with one repeater Switch repeater VN2001 in port P1 VN2001 in port P0 Switch 1 Not connected PoE Repeater PoE Neutral p...

Page 22: ...ernet distance between two nodes maximum 300 ft 100 m Repeater power supply via Power over Ethernet PoE from the VN2001 For each switch node 1 repeater can be supplied with power The switch carries out ground fault supervision as far as the repeater If there are two repeaters the first one transfers ground fault supervision to the second repeater MoNet PMI Mainboard Ethernet P2 P3 P4 P5 P0 P1 POWE...

Page 23: ... 5 Jumper settings on the VN2001 The slots the jumpers are plugged into on the Ethernet module electric differ depending on how the module will be used The table below shows the different settings for the corresponding function Figure 16 View of VN2001 with jumper strip X102 1 24V RxT GND 24V TxT GND 1 8 X102 ...

Page 24: ..._d_en_ Siemens Industry Inc 2018 09 07 X102 jumper strip Jumper setting on X102 Function Ground fault supervision activated PoE activated Neutral position function deactivated PoE for cables crossed at one end 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 ...

Page 25: ... only the case if the Ethernet switch modular is installed remotely in another device The power supply must be a DC 24 V power supply featuring regulated and power limited output that has been approved for fire alarm signal applications Designation Description A Supply input 1 DC 24 V A Common supply input 1 DC 0 V B Not connected B Not connected Admissible cable cross section AWG 24 AWG 12 0 2 2 ...

Page 26: ...llowing fault messages can be configured via the web interface Fatal fault Ethernet switch modular malfunction Ring fault Ring faults are only displayed if the Ethernet switch modular has the function of the redundancy manager Ring port fault Link down state of a ring port Pin Designation Description F1 OUT Dry contact relay 1 common normally open F2 OUT Dry contact relay 2 common normally open F3...

Page 27: ...lashing pattern every 2 s Normal Operation Normal operation FW Update Mode Ready for firmware update FW Update Running Ethernet switch is loading firmware FW Update Failed FW update could not be completed network connection may have been interrupted Checksum Failed Incorrect firmware checksum Fatal FAULT Ethernet switch is generating some other fault Table 2 FAULT LED flashing pattern t 0 125 250 ...

Page 28: ...edundancy manager Within each MRP 1 ring there has to be a master Ethernet switch All the other Ethernet switches must perform the role of clients Function indicator Meaning RM LED flashing pattern every 2 s Search Manager Ethernet switch is being initialized System is looking for MRP manager Topology has changed because Ethernet ring participants have been added or removed Manager Ethernet switch...

Page 29: ...has to be configured within each MRP ring Ring open Check the MRP ring There is a break in the ring at one or more of the panels Check whether cable is defective Ring port LEDs which are switched off show open ports Defective unplugged cable Double manager Adapt configuration Only one Ethernet switch is allowed to be configured as the ring manager Unidirectional Data Link Fault Check the cabling o...

Page 30: ... for RESET key FAULT LED Function Press for 5 s Not lit up Hardware reset The Ethernet switch modular is restarted immediately after pressing the reset key Press for between 5 10 s Lit up Factory reset The Ethernet switch modular is restored to the factory settings Press for 10 s Lights up and goes out as soon as the switch is in update mode The switch is in firmware update mode The reset key can ...

Page 31: ...s made or a hardware reset must be performed afterward Switch position IP address operating mode Sub net mask operating mode 0 Configured via web interface or MoNet bus Factory setting 0 0 0 0 Configured via web interface or MoNet bus Factory setting 255 255 248 0 1 192 168 99 241 255 255 248 0 2 192 168 99 242 255 255 248 0 3 192 168 99 243 255 255 248 0 4 192 168 99 244 255 255 248 0 5 192 168 9...

Page 32: ...MC protection Ground fault supervision Circuits All connections are power limited All connections except local and MoNet connections are supervised Module connections optional Ethernet module electric VN2001 RJ45 connection TP cable length max 330 ft 100 m Ethernet module MM VN2002 LC connector multi mode fiber optic Fiber length 62 5 125 µm 13123 ft 4 km with an 11 dBm loss 1 Fiber length 50 125 ...

Page 33: ...can radiate radio frequency energy and if not installed and used in accordance with the instructions manual may cause interference to radio communications It has been tested and found to comply with the limits for a Class pursuant to Part 15 of FCC Rules which are designed to provide reasonable protec against such interference when operated in a commercial environment Operation of this equipment i...

Page 34: ...ision 8 Fernwood Road Florham Park NJ 07932 1 973 593 2600 www sbt siemens com FIS Siemens Industry Inc 2015 Technical specifications and availability subject to change without notice Document ID A6V10407862_d_en_ SAP order no A5Q00060099 Edition 2018 09 07 ...

Reviews: