Fiber network module FN2006 / FN2007
Indicators
1
13
Siemens Industry, Inc.
A6V10315048_b_en_US
Building Technologies Division
01/13/2012
Terminal Plug
without housing
Connector
Cover cap (open)
1 2 3
A1
A2
B1
B2
Terminal Plug
with housing
360º shielding
Connector EF1/EF2, FCnet/C-WEB A1/B1 (A2/B2)
1.5
Indicators
LED
Colour Function
Condition Meaning
RX1
Green
Receipt of data from fiber optic circuit '1' Lit up
Data is being received from circuit '1'
Fail1
Yellow Fault on fiber optic circuit '1'
Lit up
Weakly receiving data from circuit '1'
Fail2
Yellow Fault on fiber optic circuit '2'
Lit up
Weakly receiving data from circuit '2'.
RX2
Green
Receiving data from fiber optic circuit '2' Lit up
Data is being received from circuit '2'
On
Normal operation (feeding voltage available)
Power B Green
Supervision of feeding voltage for
'Power B'
Off
No feeding voltage or voltage below minimum
input voltage (9 V)
On
Normal operation (feeding voltage available)
Power A Green
Supervision of feeding voltage for
'Power A'
Off
No feeding voltage or voltage below minimum
input voltage (9 V)
LNK1
Green
Data transmission for FCnet/C-WEB
circuit '1'
Flashes
Data is being transmitted via A1/B1
EF1
Yellow Ground fault supervision on
FCnet/C-WEB circuit '1'
Lit up
Ground fault on A1/B1
EF2
Yellow Creation of ground fault on
FCnet/C-WEB circuit '2'
Flashes
Ground fault on A1/B1 mirrored on A2/B2
LNK2
Green
Data transmission for FCnet/C-WEB
circuit '2'
Flashes
Data is being transmitted via A2/B2