Fiber network module FN2006 / FN2007
1
Pin assignments
10
Siemens Industry, Inc.
A6V10315048_b_en_US
Building Technologies Division
01/13/2012
FCnet/C-WEB wiring
You will find detailed information about FCnetC-WEB wiring and the network module
(SAFEDLINK) FN2001 in the corresponding description.
Electrical FCnet/C-WEB supply line, shielded or unshielded. If the supply line is
shielded, cable glands must be used for the network module (SAFEDLINK). You
will find information about this in the description of the network module
(SAFEDLINK).
Ground faults detected at <1 kΩ
Total length of electrical FCnet/C-WEB wiring: Max. 3300 ft
Each pair individually supervised