7
Maintenance / Repair
Status query
36
Building Technologies
010095_j_en_--
Fire Safety
2013-02-22
7
Maintenance / Repair
7.1
Status query
The alarm sounder with additional optical indicator FDS229 has a proximity
interface (MC link).
Using this interface, it is possible to read out data from the device in a proximity
method over short distances with the detector exchanger and tester FDUD292 or
the intelligent detector tester FDUD293.
You will find more information in documents 007227 and 009718.
Status queries with detector exchanger and tester FDUD292 or intelligent
detector tester FDUD293 are only possible with devices of the 'Sinteso' product
line on the FDnet.
The following actions can be performed from the control panel:
Configure sounds
Commissioning
Activate / deactivate sound
Activate / deactivate additional optical indicator
Read error list / status register
7.2
Function check
The devices are automatically subjected to a performance check during the self-
test. Nevertheless, it is necessary to check the devices on site at regular intervals.
Recommendation:
Check the devices every year.
Replace heavily soiled or damaged devices.
No other special maintenance work is necessary.
You will find more detailed information in the control panel documentation.