4
Undertaking modernization
Step 2: Replacing the control panel and changing over to FDnet-Ex/C-NET-Ex protocol
4.2
Step 2: Replacing the control panel and changing
over to FDnet-Ex/C-NET-Ex protocol
4.2.1
Replacing the control panel or installing a line card
During modernization, we would recommend replacing the existing fire control
panel with a control panel Sinteso FC20xx or Cerberus PRO FC72x.
In the case of the 'AlgoRex' and 'SIGMASYS' product lines,
a line card (FDnet/C-NET) can be fitted in the existing fire control panel (E3M141,
FDC).
Control panel
Line card
Order number
AlgoRex
E3M141
S54405-A9-A1
SIGMASYS
FDC
S54230-B150-A2
4.2.2
Replacing the remaining peripheral devices
When changing over to the FDnet-Ex/C-NET-Ex, all peripheral devices on a
detector line which have not been modernized must be replaced. This applies to
the following device groups in particular:
All manual call points
– Replace the manual call points with manual call points FDM233-Ex
The alarm indicators must be replaced with alarm indicators FDAI9x-Ex.
Migrating the detector line from 'Collective' to 'Addressed'
The starting point is a collective detector line in which no multiple protocol
detectors are installed yet (bottom detector line in the diagram) or a detector line
which already has all of or some of the multiple protocol detectors installed (top
detector line in the diagram).
DC1192
SB3
SB3
DC1192
Collective Ex-line
Collective Ex-line
DT1101A-
Ex
DO1101A-
Ex
DT1102A-
Ex
DM1103
EOL22
(Ex)
EOL22
(Ex)
Non-Ex Area
Ex Area
FDOOT241-A9-Ex/
OOH740-A9-Ex
20
Building Technologies
A6V10443621_a_en_--
Fire Safety