Siemens FDOOT241-A9-Ex Technical Manual Download Page 1

 

 

 

 

 
Modernizing fire detection 

installations with multiple 

protocol detectors in areas at 

risk of explosion 

Technical Manual 

 

 

 

A6V10443621_a_en_-- 

Building Technologies 

2014-09-01 

 

Control Products and Systems 

Summary of Contents for FDOOT241-A9-Ex

Page 1: ...Modernizing fire detection installations with multiple protocol detectors in areas at risk of explosion Technical Manual A6V10443621_a_en_ Building Technologies 2014 09 01 Control Products and Systems ...

Page 2: ...ss authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Switzerland Ltd Infrastructure Cities Sector Building Technologies Division International Headquarters Gubelstrasse 22 CH 6301 Zug Tel 41 41 724 2424 www siemens com buildingtechnologies Edition 20...

Page 3: ...zation 15 4 1 1 Base replacement 16 4 1 2 Configuration of detector type 17 4 1 3 Test the detectors 18 4 1 3 1 Test methods 18 4 1 3 2 Testing detectors without detector exchanger and tester detector tester 19 4 1 3 3 Setting the detector zones to Test 19 4 1 4 Starting up from collective mode 19 4 2 Step 2 Replacing the control panel and changing over to FDnet Ex C NET Ex protocol 20 4 2 1 Repla...

Page 4: ...4 Building Technologies A6V10443621_a_en_ Fire Safety 2014 09 01 ...

Page 5: ...itable specialist training for the function and for the products Has attended the training courses for Product Managers Project Manager Coordinates the deployment of all persons and resources involved in the project according to schedule Provides the information required to run the project Has obtained suitable specialist training for the function and for the products Has attended the training cou...

Page 6: ...document corresponds to the recommendation of international standard ISO 8601 format YYYY MM DD Conventions for text marking Markups Special markups are shown in this document as follows Requirement for a behavior instruction 1 2 Behavior instruction with at least two operation sequences Version option or detailed information for a behavior instruction Intermediate result of a behavior instruction...

Page 7: ...could lead to an explosion The conditions for intrinsic safety are defined in EN 60079 11 FDnet C NET Addressed detector line FDnet Ex C NET Ex Addressed intrinsically safe detector line in the area at risk of explosion GMT Limit value detection technology Collective detector line Unaddressed detector line Collective Ex detector line Non addressed intrinsically safe detector line in the area at ri...

Page 8: ...ase FDB20x FDB201 AA FDB22x FDB221 AA Base attachment FDB291 Detector designation plate FDBZ291 Dummy detector FDX291 A6V10210362 FS720 Fire detection system Planning A6V10210424 FS720 Fire detection system Configuration A6V10229261 List of compatibility for Cerberus PRO product line A6V10324618 Planning Mounting Installation Commissioning Maintenance of fire detection installations with addressed...

Page 9: ...nstead of a if the reference document is already this version The table below shows this document s history of changes Modification index Edition date Brief description a 2014 09 01 First edition The table below shows the published language versions with the corresponding modification index Modification index en_ de_ fr_ it_ es_ a X X X X X X published no publication with this modification index 9...

Page 10: ...cteristics of multiple protocol detectors The multiple protocol detectors FDOOT241 A9 Ex and OOH740 A9 Ex may communicate via different detector line protocols These detectors automatically recognize the protocol on the detector line e g FDnet Ex C NET Ex or collective Ex and switch to this protocol This functionality simplifies detector line commissioning during modernization because additional m...

Page 11: ... modern sensitive fire detection installations with false alarm immunity This document does not cover modernization via the control panel with a line card of an alternative protocol e g collective Step 1 Replacing the existing point detectors with multiple protocol detectors The detectors communicate with the protocol of the installed system collective Ex No changes are required on the fire contro...

Page 12: ...ging over to FDnet Ex C NET Ex Limitations exist when connecting external alarm indicators You will find more information in chapter Limitations on detector families Only the stub topology is permitted in areas at risk of explosion The following are not admissible Loop Sub stub on loop Sub stub on sub stub Sub stub on stub Several stub branches from one location You will find information about det...

Page 13: ...unt When using a point detector FDOOT241 A9 Ex or OOH740 A9 Ex on a collective Ex detector line you must observe the following points Only a stub topology is permitted for intrinsically safe collective Ex detector lines and FDnet Ex C NET Ex detector lines You will find more information in documents 001204 and A6V10324618 When using an AlgoRex point detector via an FDOOT241 A9 Ex or OOH740 A9 Ex t...

Page 14: ...ors Detector family Point detectors which can be replaced Replaced with Multiple protocol detectors Base adapter Collective Ex Siemens Cerberus DO1101A Ex DT1101A Ex DT1102A Ex FDOOT241 A9 Ex OOH740 A9 Ex The point detectors FDOOT241 A9 Ex and OOH740 A9 Ex may not be installed using base adapters 14 Building Technologies A6V10443621_a_en_ Fire Safety 2014 09 01 ...

Page 15: ...y personnel who are not sufficiently qualified Risk of explosion Work in potentially explosive areas may only be carried out by qualified specialists or by specially instructed persons in accordance with the national and international directives and regulations Point detectors that can only be operated in collective mode are replaced with multiple protocol detectors The detector lines are still op...

Page 16: ... incorrect detector bases in the area at risk of explosion Risk of explosion When modernizing the collective Ex detector line point detectors FDOOT241 A9 Ex and OOH740 A9 Ex may only be used with detector bases FDB20x or FDB22x Do not use detector bases from the AlgoRex product range or base adapters You will find information about installing the detector bases FDB20x and FDB22x in document A6V102...

Page 17: ...9 Ex or OOH740 A9 Ex is intended to replace a heat detector Also install a standard resistor to set another parameter set Determine the resistance required using the table below Install the resistor as shown in the diagram The point detector FDOOT241 A9 Ex or OOH740 A9 Ex is installed and configured Installing the parameter set resistor R in the detector base R Values for the parameter set resisto...

Page 18: ...F8 8S Hot air RE7T Detector exchanger and tester or intelligent detector tester FDUD292 FDUD293 You will find more information about the testers in document 007228 See chapter Applicable documents WARNING Using non intrinsically safe devices in areas at risk of explosion Risk of explosion Do not use the detector exchanger and tester FDUD292 or the intelligent detector tester FDUD293 in areas at ri...

Page 19: ...f the detector group is switched to Test on the control panel Detectors on a collective Ex detector line are switched to test mode for 3 minutes in the following cases Starting up and resetting the detector line Inserting the detector Removing the detector from the detector line and re inserting it To trigger a detector using test gas normally 2 4 gas discharges at intervals of approx 2 seconds ar...

Page 20: ...er to the FDnet Ex C NET Ex all peripheral devices on a detector line which have not been modernized must be replaced This applies to the following device groups in particular All manual call points Replace the manual call points with manual call points FDM233 Ex The alarm indicators must be replaced with alarm indicators FDAI9x Ex Migrating the detector line from Collective to Addressed The start...

Page 21: ...9 Ex FDM223 Ex FDnet FDnet FDnet Ex FDCL221 Ex FDCL221 Ex Non Ex Area Ex Area C NET Ex Use the multiple protocol detector OOH740 A9 Ex OOH740 A9 Ex C NET Ex OOH740 A9 Ex OOH740 A9 Ex OOH740 A9 Ex FDM223 Ex C NET C NET C NET Ex FDCL221 Ex FDCL221 Ex Non Ex Area Ex Area If the national and regional regulations in your country permit automatic fire detectors and manual call points to be operated on a...

Page 22: ...munication between the control panel and all subsequent detectors is interrupted A fault is indicated on the control panel Remove the diodes in the detector bases in the case of mixed collective Ex detector lines to which manual call points and point detectors are connected Check whether only permitted topologies are being used Only the stub topology is permitted The maximum possible number of per...

Page 23: ...using the relevant configuration software for the fire control panel You will find information about configuration with the software for the respective fire detection system in the following documents Fire detection system Software Document ID FS20 SintesoWorks 009078 FS720 Cerberus Engineering Tool A6V10210424 See chapter Applicable documents 8 23 Building Technologies A6V10443621_a_en_ Fire Safe...

Page 24: ...se Replacement 16 Sinteso 16 Detector line Topology 12 Detectors devices which cannot be replaced 12 Documentation for fire detection system 8 Download center URL 8 L Line card Replacing 11 List of compatibility 8 S Step by step modernization 11 T Topology 12 24 Building Technologies A6V10443621_a_en_ Fire Safety 2014 09 01 ...

Page 25: ...Index 25 Building Technologies A6V10443621_a_en_ Fire Safety 2014 09 01 ...

Page 26: ...ernational Headquarters Gubelstrasse 22 CH 6301 Zug Tel 41 41 724 24 24 www siemens com buildingtechnologies 2014 Copyright Siemens Switzerland Ltd Technical specifications and availability subject to change without notice Document ID A6V10443621_a_en_ Manual FD20 FD720 Edition 2014 09 01 Section 8 ...