5.2 Installation
180°
4
9
8
13
8
12
10
2
14
3
11
7
8
9
5
6
1
11
11
15
1 Back box
9 Screws for switching unit
2 Battery pack BAT3.6-10
1
10 Internal alarm indicator
3 Type plate with adhesive label
11 Plastic/glass insert
4 Battery holders
12 Housing cover
5 Battery connector
13 Retainer
6 Housing switching contact
14 Spring
7 Switching unit
15 Triggering device
8 Stop
1
not included in the scope of delivery
The flashing behavior of the internal alarm indicator is described in document
A6V10401120 in the 'Internal alarm indicator' chapter.
w
The back box is fastened.
w
You have a new, undamaged battery pack to hand.
w
You have key FDMK295 and a Phillips screwdriver to hand.
w
The radio gateway has been activated and switched to maintenance mode.
1. Remove the adhesive label with the serial number from the type plate (3) on
the switching unit. Use the adhesive label to mark the position of the radio
manual call point FDM275 on the device location plan.
2. Label the battery pack (2) with the current date.
3. If the switching unit (7) needs to be switched to 'factory setting'
Mounting and installation
Installation
5
A6V10401120_g_en_--
27 | 46