6
Commissioning
Checking function
32
Building Technologies
A6V10374021_c_en_--
Fire Safety
2014-07-01
Enabling on FC72x fire control panels
1. In the main menu, select the 'Functions' menu item.
The 'Functions' window is open.
2. Select 'Maintenance' and confirm with <ok>.
A list of all element categories on which a command of the 'Maintenance'
command group can be executed is indicated.
3. Select the 'Element category' 'Station'.
The 'Enter address' window is open.
4. Enter the number of the 'Station' on which you want to enable communication
with the detector exchanger and tester and confirm with <ok>.
The 'Select command' window is open.
5. Select the 'Enable MC link' command and confirm with <ok>.
Communication is now enabled.
Automatic deactivation of test mode, e.g. for FC20xx/FC72x:
Once a specified time has elapsed, deactivation occurs after 60 seconds.
Deactivation occurs immediately when a customer text, for example, is
downloaded.
Deactivation occurs immediately when the double CPU is changed over.
The manual call point is installed and electrically connected. See the chapter
'Installation [ 25]'.
1. Push the keyhole cover to the side.
2. Open the door of the manual call point with the key.
Test mode is activated.
The LED flashes green; this means the detector is in test mode. It is
possible for the flashing to begin after a delay of up to five seconds.
3. Check whether test mode is activated and whether the LED is flashing green.
4. If the LED is not flashing green, close the door and start again with step 1.
-
NOTICE! If the alarm button is pressed when the LED is not flashing green,
a genuine alarm will be activated.
5. If the LED is flashing green, press the alarm button immediately.
The test alarm is transmitted. The LED also flashes red by way of
confirmation.
6. Place the key (1) onto the round guide and turn it clockwise so that the black
stopping lever (2) is pushed downward.
The alarm button pops out audibly by approx. 3 mm.
7. Close the door of the manual call point.
Test mode is deactivated.
8. Close the keyhole cover.
9. Check whether an alarm is displayed on the fire control panel.
The manual call point is ready for operation again.