Planning
Compatibility
22
Building Technologies
A6V10374021_c_en_--
Fire Safety
2014-07-01
4 Planning
4.1 Compatibility
Compatible with control panels that support the FDnet/C-NET detector line.
Detector line
Control panel
FC20xx
FC72x
SIGMASYS
AlgoRex
FDnet
X
-
–
–
C-NET
–
X
–
–
X = compatible
– = not compatible
You will find details in the 'List of compatibility'.
4.2 Fields of application
The manual call points are intended for use in places where a fire can be detected
by people who can manually trigger an alarm.
4.3 Installation site
The manual call points must be installed in easily accessible places at a height of
0.9...1.6 m on an even surface.
Observe the country-specific regulations for the exact installation height!
4.4 Environmental influences
If the devices are used in industrial applications, consultation with the project
manager is required, since plastics do not withstand certain environmental
conditions.
The following factors must be taken into consideration:
Chemicals
Temperature
Moisture