Control Products and Systems

FDM243H
Manual call point

Technical Manual

Summary of Contents for FDM243H

Page 1: ...A6V10374021_c_en_ Building Technologies 2014 07 01 Control Products and Systems FDM243H Manual call point Technical Manual ...

Page 2: ...on of its contents and communication thereof to others without express authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Switzerland Ltd Infrastructure Cities Sector Building Technologies Division International Headquarters Gubelstrasse 22 CH 6301 Zu...

Page 3: ...al call point 16 3 2 2 Connections 17 3 2 3 Indication elements 17 3 3 Function 18 3 3 1 Danger levels 18 3 3 2 Internal alarm indicator 18 3 3 3 Line separator 18 3 3 4 Test mode on the manual call point 19 3 3 5 Diagnosis levels 20 3 3 6 Behavior in degraded mode 20 3 4 Accessories 21 3 4 1 Glass insert FDMG298 21 3 4 2 Key FDMK294 21 3 4 3 M20 x 1 5 metal cable gland 21 4 Planning 22 4 1 Compat...

Page 4: ...enance Repair 33 7 1 Resetting after an alarm 33 7 2 Status query 34 7 3 Function check 34 7 4 Replacing the glass insert 35 8 Specification 37 8 1 Technical data 37 8 2 Dimensions 38 8 3 Master gauge for recesses 39 8 4 Environmental compatibility and disposal 39 Index 40 ...

Page 5: ...as attended the training courses for Project Managers Project engineer Sets parameters for product depending on specific national and or customer requirements Checks operability and approves the product for commissioning at the place of installation Is responsible for trouble shooting Has obtained suitable specialist training for the function and for the products Has attended the training courses ...

Page 6: ...entary information and tips The i symbol identifies supplementary information and tips for an easier way of working 1 1 Applicable documents Document ID Title 008250 Technical Manual Line tester FDUL221 008331 List of compatibility for Sinteso product line 008838 Operation Manual Fire control panel Fire terminal FC20xx FT2040 009052 FS20 Fire detection system Commissioning Maintenance Troubleshoot...

Page 7: ...cation index Edition date Brief description c 2014 07 01 Installation height changed from 1 3 1 6 m to 0 9 1 6 m V pins removed from accessories b 2013 09 18 Approvals supplemented Key for FDMK294 modified a 2013 02 01 First edition The language versions and country variants produced by a local company have the same modification index as the corresponding reference document They are not however in...

Page 8: ... dangers the type of danger or possible consequences measures and prohibitions examples of which are shown in the following table General danger Explosive atmosphere Voltage electric shock Laser light Battery Heat Signal word The signal word classifies the danger as defined in the following table Signal word Danger level DANGER DANGER identifies a dangerous situation which will result directly in ...

Page 9: ... is shown as follows WARNING Nature and origin of the danger Consequences if the danger occurs Measures prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows NOTICE Nature and origin of the danger Consequences if the danger occurs Measures prohibitions for danger avoidance ...

Page 10: ...cordance with the electrotechnical regulations Wherever possible disconnect products from the power supply when carrying out commissioning maintenance or repair work on them Lock volt free areas to prevent them being switched back on again by mistake Label the connection terminals with external external voltage using a DANGER External voltage sign Route mains connections to products separately and...

Page 11: ...aults malfunctioning and safety risks Written confirmation must be obtained from Siemens and the corresponding safety bodies for modifications or additions Modules and spare parts Components and spare parts must comply with the technical specifications defined by Siemens Only use products specified or recommended by Siemens Only use fuses with the specified fuse characteristics Wrong battery types...

Page 12: ...njury and damage to property in the event of a fire Read the Release Notes before you plan and or configure a fire detection installation Read the Release Notes before you carry out a firmware update to a fire detection installation NOTICE Incorrect planning and or configuration Important standards and specifications are not satisfied Fire detection installation is not accepted for commissioning A...

Page 13: ... consists of a housing and a switching unit It has the following features Indirect activation Door contact connected with magnet Two wire installation for all cable types Cable entry from below for two surface mounted feed lines Individual detector addressing Indication of the condition Alarm localization or test by means of a dichromatic LED Integrated line separation function Communication via F...

Page 14: ...en_ Fire Safety 2014 07 01 3 1 1 Details for ordering Manual call point FDM243H Type Order no Designation FDM243H S54311 F8 A1 Manual call point Scope of delivery Red housing with glass insert and switching unit 1 key 1 V pin M20 x 1 5 2 screws 2 pins See also Accessories 20 ...

Page 15: ... on the packaging label Details of the product version can be found directly on the packaging label in the barcode ES Example of a packaging label with details of the product version Product version on the product label and the type plate Details of the product version can be found after the device order number ES 04 Example of a product label with details of the product version Depending on the p...

Page 16: ...ation The alarm is immediately transmitted to the control panel When the alarm is activated the switching unit must be reset and a new glass insert installed 2 3 4 5 6 7 1 8 9 10 11 Manual call point FDM243H with open door 1 Housing 7 Switching magnet for door contact 2 Switching unit 8 Retainer for glass insert 3 Alarm button 9 Guide for the glass insert 4 Internal alarm indicator 10 Stopping lev...

Page 17: ...manual call point has eight spring clips on the rear of the switching unit these are for the detector line and for connecting external alarm indicators Spring clips on the rear of the switching unit 3 2 3 Indication elements An LED is built into the switching unit as an internal alarm indicator Internal alarm indicator ...

Page 18: ...icator of the alarm indicator has the following meanings LED indication Meaning Off Normal condition Green Flashes once per second Test mode is active Red Flashes once per second Localization is active o r Alarm is triggered Red and green alternating Flashes twice per second Alarm is triggered localization is active a n d Test mode is active 3 3 3 Line separator All FDnet C NET devices are equippe...

Page 19: ...anel MC link communication for example must be active Enabling on FC20xx fire control panels You will find more information for FC20xx fire control panels in Enabling detector exchanger and tester communication in document number 008838 Enabling on FC72x fire control panels 1 In the main menu select the Functions menu item The Functions window is open 2 Select Maintenance and confirm with ok A lis...

Page 20: ...ol panel is in degraded mode operation Depending on the control panel type the fire control panel can continue to perform the most important alarming and signaling functions in degraded mode operation Behavior of control panels that support degraded mode operation Alarming is still ensured in degraded mode operation However in degraded mode only collective alarming is possible This means that in t...

Page 21: ...points To help with resetting the alarm button Compatible with Manual call point FDM223 Manual call point FDM234 Manual call point FDM243H Order no S24217 G34 A1 3 4 3 M20 x 1 5 metal cable gland For introducing a cable into a housing For cable diameters of 3 5 5 5 mm Temperature range 40 100 C Allows for increased IP protection Compatible with M20 x 1 5 metal counter nut Housing FDMH231 S R Housi...

Page 22: ...s are intended for use in places where a fire can be detected by people who can manually trigger an alarm 4 3 Installation site The manual call points must be installed in easily accessible places at a height of 0 9 1 6 m on an even surface Observe the country specific regulations for the exact installation height 4 4 Environmental influences If the devices are used in industrial applications cons...

Page 23: ... A6V10374021_c_en_ Fire Safety 2014 07 01 5 Mounting Installation The manual call point is mounted and installed in three steps 1 Preparation see the chapter Preparation 2 Installation see the chapter Installation 3 Electrical connection see the chapter Installation ...

Page 24: ...Push the keyhole cover 2 to the right 2 Open the door with the key supplied 1 3 Pull out the key and keep it in a safe place 4 Close the keyhole cover Do not unscrew the four cross head screws on the switching unit 5 Unscrew the four Allen head screws 3 and remove the switching unit 4 6 Determine how the cable should be entered in the housing from below Remove the cable gland 6 which is not requir...

Page 25: ...ation See the chapter Preparation 23 1 Secure the housing at a height of 0 9 1 6 m on an even surface See the chapter Master gauge for recesses 39 Only use the screw holes marked with arrows see diagram below 2 Pull the cables through the entry opening s into the housing 3 Tighten the cable gland so that it is properly sealed The manual call point is now prepared for electrical connection Screw ho...

Page 26: ...e applied to the lines WARNING Deactivating the manual call points prevents alarms from being forwarded Alarming does not take place Mark deactivated manual call points or those which are not fully functional with the notice NOT IN USE Do not remove the NOT IN USE notice until commissioning is about to begin NOT IN USE label Note the positive and negative poles Only connect one wire per terminal T...

Page 27: ...int is prepared for electrical connection See the chapters Preparation 23 and Installation 25 1 Connect the feed lines LINE to the spring clips in the switching unit in accordance with the connection diagram 2 If using shielded cables NOTICE The shielding must not touch any external potentials Connect the shielding of the detector line cables SHIELD Connect the shielding of the external alarm indi...

Page 28: ...ghtening the four Allen head screws 2 firmly Check whether the button is protruding by about 3 mm If the alarm button is pressed in reset it See the Checking function 29 chapter 6 Close the housing with the door The manual call point is now electrically connected 2 3 1 Installing the switching unit 1 Housing 2 Allen head screws 3 Switching unit ...

Page 29: ...ce testing The manual call points have an internal alarm indicator This internal alarm indicator may also be activated from the control panel for localization and device testing The LED indicator of the alarm indicator has the following meanings LED indication Meaning Off Normal condition Green Flashes once per second Test mode is active Red Flashes once per second Localization is active o r Alarm...

Page 30: ...ies A6V10374021_c_en_ Fire Safety 2014 07 01 6 2 Checking function Checking is usually performed from the fire control panel but it may also be performed from the manual call point 1 2 Resetting manual call point FDM243H 1 Key 2 Stopping lever for resetting ...

Page 31: ...ne to Normal operation on the fire control panel The detector line is ready for operation again Checking from the manual call point You can activate test mode in the fire control panel by opening the door and deactivate it by closing the door again Test mode is only active for a short time Therefore you should work quickly to complete the steps between opening the door and closing it again In test...

Page 32: ...uble CPU is changed over The manual call point is installed and electrically connected See the chapter Installation 25 1 Push the keyhole cover to the side 2 Open the door of the manual call point with the key Test mode is activated The LED flashes green this means the detector is in test mode It is possible for the flashing to begin after a delay of up to five seconds 3 Check whether test mode is...

Page 33: ...eparation 23 2 CAUTION Sharp remains of glass Risk of cutting injuries when removing the remains of the glass insert Remove the remains of the glass carefully 3 Remove all the remains of the old glass insert 4 Insert a new glass insert See the chapter Replacing the glass insert 34 5 Place the key 1 onto the round guide and turn it clockwise so that the black stopping lever 2 is pushed downward The...

Page 34: ...l documentation Document 009052 applies to fire control panels FC20xx Document A6V10333448 applies to fire control panels FC72x 7 3 Function check The devices are automatically subjected to a performance check during the self test Nevertheless it is necessary to check the devices on site at regular intervals Recommendation Check the devices every year Replace heavily soiled or damaged devices No o...

Page 35: ... follows The door 1 of the manual call point is open See the chapter Preparation 23 1 Remove all the remains of the old glass insert 2 Push the black retainer 2 to the right 3 Place the new glass insert 3 under both guides 4 4 Push the black retainer 2 to the left over the glass insert 5 Check the function of the manual call point The glass insert has been replaced 2 4 3 1 Installing the glass ins...

Page 36: ...rm button The alarm button is pressed The door is open Place the key 1 onto the round guide and turn it clockwise so that the black stopping lever 2 is pushed downward The switching unit clicks and the alarm button is now protruding by approx 3 mm The alarm button has been reset 1 2 Resetting the alarm button 1 Key 2 Stopping lever ...

Page 37: ...rrent connection factor 1 Address connection factor 1 Separator connector factor 1 Protocol FDnet C NET System compatibility See List of compatibility Line separator Line voltage Nominal DC 32 V Vnom Minimum DC 12 V Vmin Maximum DC 33 V Vmax Voltage at which the line separator opens Minimum DC 7 5 V VSO min Maximum DC 10 5 V VSO max Permanent current when switches are closed Max 0 5 A IC max Switc...

Page 38: ...5 70 C Storage temperature 40 70 C Air humidity no moisture condensation 95 rel Protection categories according to EN 60529 IEC 60529 IP66 Environmental category according to EN 54 11 Outdoors Electromagnetic compatibility 10 kHz 2 7 GHz 50 V m Mechanical data Design according to EN 54 11 Type B indirect activation Housing material Polycarbonate PC Color RAL 3000 flame red Dimensions L x W x H 136...

Page 39: ...following measures have been undertaken Use of reusable materials Use of halogen free plastics Electronic parts and synthetic materials can be separated Larger plastic parts are labeled according to ISO 11469 and ISO 1043 The plastics can be separated and recycled on this basis Electronic parts and batteries must not be disposed of with domestic waste Take electronic parts and batteries to local c...

Page 40: ...ng the communication with the detector exchanger and tester 19 31 Environmental compatibility 39 Environmental influences 22 ES Product version 15 EU directives 37 37 F Fire control panel failure Degraded mode operation 20 I Impact Chemicals 22 Moisture 22 Temperature 22 Internal alarm indicator 18 29 L Line separator Function 18 List of compatibility 6 20 22 M Maintenance intervals 34 P Packaging...

Page 41: ...Index 41 Building Technologies A6V10374021_c_en_ Fire Safety 2014 07 01 ...

Page 42: ...ational Headquarters Gubelstrasse 22 CH 6301 Zug Tel 41 41 724 24 24 www siemens com buildingtechnologies 2013 2014 Copyright Siemens Switzerland Ltd Technical specifications and availability subject to change without notice Document ID A6V10374021_c_en_ Manual FD20 FD720 Edition 2014 07 01 Register 4 ...