Manual call point FDM223H
w
The manual call point is installed and electrically connected. See the chapter
'Installation [➙ 31]'.
1. Set the detector line to 'Test' on the control panel.
2. Open the door of the manual call point with the Allen key.
3. Press the alarm button.
a
The alarm signal is transmitted.
4. Check whether an alarm is displayed on the fire control panel.
5. Push the black locking lever (1) in the top right-hand corner to the right until it
clicks.
a
The alarm button is now protruding by approx. 5 mm.
6. Close the door of the manual call point.
a
The manual call point is ready for operation again.
7. Set the detector line to 'Normal operation' on the control panel.
a
The detector line is ready for operation again.
1
Figure 21: Resetting manual call point FDM223H
1
Locking lever
Commissioning
Checking function
6
007002_k_en_--
41 | 54