Specifications
Technical data
8
29 | 32
Building Technologies
A6V10201150_d_en_--
Fire Safety
2018-12-19
8 Specifications
8.1 Technical data
Detector line
Operating voltage
DC 16…26 V
Quiescent current
0.01 mA
Alarm current (permanent, maximum) 60 mA
Alarm current (pulsating)
100 mA
Maximum current connection factor
1
Quiescent current connection factor
1
Protocol
Collective (SynoLINE600)
Compatibility
Refer to document 'List of compatibility';
doc. no. 008331
Connections
Detector line:
●
Design
Screw terminals
●
Cable cross section
0.28…1.5 mm
2
Ambient conditions
Operating temperature
-25…+70 °C
Storage temperature
-30…+75 °C
Air humidity
≤
95 % rel.
Protection category (IEC60529)
IP44
Electromagnetic compatibility at:
●
10 MHz…1 GHz
50 V/m
●
1 GHz…2 GHz
10 V/m
Mechanical data
Dimensions (L x W x H):
●
FDM1101-Rx
87 x 87 x 20 mm
●
FDM1101-Rx with back box
FDMH295-R / FDMH295-S
87 x 87 x 53 mm
Weight:
●
FDM1101-Rx
0.097 kg
●
Back box FDMH295-R /
FDMH295-S
0.057 kg
Colors:
●
FDM1101-Rx
Red (RAL 3000)
●
Back box FDMH295-R /
FDMH295-S
Red (RAL 3000)
Material
ABS PC ASA
Standards
European standards
EN 54-11
EN 50130-4