Siemens FDK:085U0226 Operating Instructions Manual Download Page 11

HART add-on module

11

Bit

Definition

7

Device Malfunction

 – The device detected a serious error or failure that compromises device

operations. This flag is set whenever an error of category „Fatal Error“ is pending in the
flowmeter. Detailed information can be found via HART command 48.

6

Configuration Changed 

– An operation was performed that changed the device’s configuration.

Any HART command, which writes information to the flowmeter, will set this flag. The flag can
be reset using command 38. The flag is handled separately for each HART master (primary/
secondary). Note: In the flowmeter, the flag is NOT stored during power cycles.

5

Cold Start 

– A power failure or Device Reset has occurred. This flag is only set in the first

response transmitted to a Hart Master after power failure. The flag is handled separately
for each HART master (primary/secondary).

4

More Status Available

 – More status information is available via Command 48, Read Additional

Status Information. This flag is set, whenever a transmitter specific error or

warning is active

in the flowmeter.

3

Loop Current Fixed

 – The Loop Current is being held at a fixed value and is not responding to

process variations. This flag is always set, if the transmitter is in Multidrop mode – i.e. the
Hart address is not zero. This flag is also set in SingleDrop mode, if the flowmeters current
output is forced in Service Mode or via Hart Command #40.

2

Loop Current Saturated

 – The Loop Current has reached its upper (or lower) endpoint limit

and cannot increase (or decrease) any further. This flag is set whenever the flowmeters
overflow warning (error no. 30) is pending.

1

Non-Primary Variable Out of Limits

 – A Device Variable not mapped to the PV is beyond its

operating limits. This flag is always zero in the flowmeter (ie not used).

0

Primary Variable Out of Limits

 – The PV is beyound its operating limits. This flag is set

whenever the flowmeters overflow warning (error no. 30) is pending.

This chapter defines all status provided by the flowmeter including: the Device status byte; the
Extended Device Status byte; and status information returned in Command 48.

 7. Status Information

7.1

Device status

7.2

Extended device
status

The extended device status bits are not supported by the flowmeter. Value is always zero.

7.3

Additional device
status (Command
48)

Command 48 returns 25 bytes of data. Bits not listed in the table below are set to zero. For detailed
USM II error number descriptions please look in the MAG/MASS manual, Literature 1 and 2.

Byte

Bit

Meaning

Class

0

0

Set if any 

Warnings

 are active

  – See bytes18-21 below

1

Set if any 

Permanent errors

 are active – See bytes 14-17 below

mode

2

Set if any 

Fatal errors

 are active – See bytes 1-5 below

1

0-7

USM Fatal Error 60, 61, 62, 63, 70, 71, 80, 81

(bit 0 corresponds to error 60, bit 7 to error 81)

error

2

0-7

USM Fatal Error 82, 83, 84, 96, 97, 64, 65, 66

(bit 0 corresponds to error 82, bit 7 to error 66)

error

3

0-7

USM Fatal Error 67, 68, 69, 72, 73, 74, 75, 76

(bit 0 corresponds to error 67, bit 7 to error 76)

error

4

0-2

USM Fatal Error 77, 78, 79 

(bit 0 corresponds to error 77, bit 2 to error 79)

error

5

0-7

Reserved (=0)

6

0-7

Extended Device Status Not supported (=0)

mode

7

0-7

Device Operating Mode Not supported (=0

)

mode

8-10

0-7

Analog Channel Saturated Not supported (=0)

mode

11-13

0-7

Analog Channel Fixed Not supported (=0)

mode

14

0-7

USM Permanent Error 40, 41, 42, 43, 44, 45, 46, 47

(bit 0 corresponds to error 40, bit 7 to error 47)

error

15

0-7

USM Permanent Error 48, 49, 94, 95, 50, 51, 52, 53

(bit 0 corresponds to error 48, bit 7 to error 53)

error

16

0-5

USM Permanent Error 54, 55, 56, 57, 58, 59

(bit 0 corresponds to error 54, bit 5 to error 59)

error

17

0-7

Reserved (=0)

18

0-7

USM Warning 20, 21, 22, 23, 24, 30, 31, 90

(bit 0 corresponds to error 20, bit 7 to error 90)

warning

19

0-7

USM Warning 91, 92, 93, 25, 26, 27, 28,2 9

(bit 0 corresponds to error 91, bit 7 to error 29)

warning

20

0-7

USM Warning 32, 33, 34, 35, 36, 37, 38, 39

(bit 0 corresponds to error 32, bit 7 to error 39)

warning

21-24

0-7

Reserved (=0)

7.

Status Information

Summary of Contents for FDK:085U0226

Page 1: ...SITRANS F Communication Modules Add on modules HART Operating Instructions 07 2010 ...

Page 2: ......

Page 3: ... explanation 9 4 6 2 Sensorprom 9 5 Device Variables 9 6 Dynamic Variables 9 6 1 MAG 5000 C 6000 9 6 2 MASS 6000 9 7 Status Information 10 7 1 Device status 10 7 2 Extended device status 10 7 3 Additional device status Command 48 10 8 Universal Commands 11 9 Common Practice Commands 12 10 Device Specific Commands 13 11 Tables 17 11 1 Volume flow unit codes 17 11 2 Volume unit codes 18 11 3 Mass fl...

Page 4: ...r is familiar with HART Protocol requirements and terminology AOM Add On Module USMII Concept with flexible plug play fieldbus modules SensorProm Storing unit for all settings HCF HART communication foundation FSK Frequency Shift Keying physical layer CN Capacitance number capacitance as a multiple of 5000 pF pF Picofarad 10 12 Farad unit of electrical capacitance PV Primary variable SV Secondary ...

Page 5: ... is based on the flexible USM II technology This includes the AOM Add On Module that provides digital communications capabilities for the USM II transmitters This approach gives far more flexibility and greater long term protection of your signal converter investment than is possible with factory standard off the shelf signal converter designs With this easy to use system providing additional func...

Page 6: ...le The installation procedure for the HART module is as follows 4 2 Mechanical Installation MAG MASS 6000 4 Product interfaces 1 Unpack the add on module and insert it in the bottom of the signal converter as shown 19 rack mounted versions IP 67 compact versions This completes the add on module installation and the signal converter may now be connected to the terminal box Communication with the di...

Page 7: ...nections must be made Terminal 31 must be connected to 91 and terminal 32 must be connected to 92 Electrical wirering can be seen in the drawing below 4 5 Current output A true HART signal consists of a Current output combined with a HART FSK signal In order to achieve this connections must be made according to the chapter HART electrical connections When a HART module is installed the Current out...

Page 8: ...ll remain Temperature Massflow Fraction A Fraction B Pct Fraction A OFF The Current output is deactivated The Current output is forced to 3 mA to indicate a Warning Current output mode 0 20 mA Not possible 0 mA can cause HART masters to stop communicating or report errors This is because values below 4mA are used for alarms and validation of the current loop 4 20 mA Factory setting 4 20 mA Alarm F...

Page 9: ...d display 1 Press Top key for two seconds NOTE For View mode only skip steps 2 3 2 Type in password 1000 by pressing Change key two times and then press Lock key and wait for two seconds 3 The display now says Basic settings 4 Press Forward key until you reach the HART module menu item 5 Press Lock key 6 You can now cycle through all the HART settings by pressing Forward key 7 Press Top key for tw...

Page 10: ...to other than the specified PV SV TV and QV 6 1 MAG 5000 C 6000 Item Value Description HART 0 15 Device address Factory setting 00 short address TAG name 8 characters Can be used to TAG the device TAG descriptor 16 characters Can be used to describe the TAG TAG date 3 bytes Can be used to date the installation HART x xx Firmware version of the HART module SW version 6 2 MASS 6000 Meaning Units PV ...

Page 11: ... overflow warning error no 30 is pending This chapter defines all status provided by the flowmeter including the Device status byte the Extended Device Status byte and status information returned in Command 48 7 Status Information 7 1 Device status 7 2 Extended device status The extended device status bits are not supported by the flowmeter Value is always zero 7 3 Additional device status Command...

Page 12: ...in command 11 Read unique id Byte 0 5 As Command 0 associated with tag TAG 8 characters 12 Read message None Byte 0 23 Message 13 Read Tag Descriptor None Byte 0 5 Tag Date Byte 6 17 descriptor Byte 18 20 date 14 Read PV sensor number None Byte 0 2 sensor serial number Byte 3 unit code for sensor limits and min span Byte 4 7 upper sensor limit Byte 8 11 lower sensor limit Byte 12 15 minimumspan 15...

Page 13: ...ys 4 mA 41 Perform transmitter Not implemented self test 42 Perform master reset None None Set to default Busy for approx 30 seconds after reply 43 Set PV zero None None HART will respond command not implemented in the cases that PV zero is not supported by the application 44 Write PV units Byte 0 PV units code As in command 45 Trim DAC Zero Not implemented 46 Trim DAC gain Not implemented 47 Writ...

Page 14: ...te 0 3 Four bytes Byte 1 Attribute ID Byte 2 Attribute Qual Byte 3 4 Index 134 Read Float32 Byte 0 CANAPP ID Byte 0 3 Float Byte 1 Attribute ID Byte 2 Attribute Qual Comment When reading values Byte 3 Unit code with no unit the unit code must Byte 4 5 Index be 251 No unit 135 Read Float64 Byte 0 CANAPP ID Byte 0 7 Float 64 Byte 1 Attribute ID Byte 2 Attribute Qual Byte 3 4 Index 136 Read VisibleSt...

Page 15: ...Qual Byte 3 Reserved 0x00 Byte 4 5 Index 2 bytes Bytes 6 7 Unsign16 146 Write Unsigned32 Byte 0 CANAPP ID Byte 0 3 Four bytes Byte 1 Attribute ID Byte 2 Attribute Qual Byte 3 Reserved 0x00 Byte 4 5 Index 2 bytes Byte 6 9 Unsign32 147 Write VisibleString Byte 0 CANAPP ID Byte 0 Length of Message Byte 1 Attribute ID Byte 1 x User message Byte 2 Attribute Qual 32 bytes Byte 3 Reserved 0x00 Byte 4 5 I...

Page 16: ...toutput1 Byte 0 0 Off As command MASS 6000 only 1 Massflow 2 Fraction A 3 Fraction B 4 Volumeflow 5 Sensor temperature 6 Density 7 Pct Fraction A 181 Read Currentoutput1 None Byte 0 0 Off MASS 6000 only 1 Massflow 2 Fraction A 3 Fraction B 4 Volumeflow 5 Sensor temperature 6 Density 7 Pct Fraction A 182 Write Digitaloutput1 Byte 0 0 Off As command 1 Pulse 2 Frequency 3 Error level 4 Error number 5...

Page 17: ...izer reset 6 Force output 7 Freeze output 8 Qmax 2 night 9 Manual Cleaning MASS 6000 Byte 0 0 Off 1 Start Batch 2 Hold continue Batch 3 Stop Batch 4 Zero Adjust 5 Totalizer reset 6 Force output 7 Freeze output 187 Read Digitalinput1 None MAG 5000 C 6000 Byte 0 0 Off 1 Start Batch 2 Hold continue Batch 3 Stop Batch 4 Zero Adjust 5 Totalizer reset 6 Force output 7 Freeze output 8 Qmax 2 night 9 Manu...

Page 18: ...per second 29 Cubic meters per day 30 UK gallons per hour 31 UK gallons per day 122 Normal liters per hour Same as l h 130 Cubic feet per hour 131 Cubic meters per minute 136 US gallons per hour 137 UK gallons per second 138 Liters per hour 235 US gallons per day 240 Milli liters per second 241 Milli liters per minute 242 Milli liters per hour 243 Hector liters per second 244 Hecto liters per minu...

Page 19: ...cond 71 Grams per minute 72 Grams per hour 73 Kilograms per second 74 Kilograms per minute 75 Kilograms per hour 76 Kilograms per day 77 Metric tons per minute 78 Metric tons per hour 79 Metric tons per day 80 Pounds per second 81 Pounds per minute 82 Pounds per hour 83 Pounds per day 84 Short tons per minute 85 Short tons per hour 86 Short tons per day 87 Long tons per hour 88 Long tons per day 2...

Page 20: ... Bits of additional device status 76 bits informational 25 bytes in total Alternative operating modes No Burst Mode Yes Write protect No 12 Performance 12 1 Sampling rates MAG 5000 C 6000 PV digital calculation Volume flow Equals the Excitation frequency SV digital calculation Totalizer 1 2 per second TV digital calculation Totalizer 2 Batch 2 per second Analog output update Equals the Excitation ...

Page 21: ... Siemens A S Flow Instruments Nordborgvej 81 DK 6430 Nordborg Subject to change without prior notice Order No A5E03089708 Lit No A5E03089708 01 SFIDK PS 023 F2 02 Siemens AG 07 2010 For more information www siemens com flow A5E03089708 ...

Reviews: