SIEMENS Industry, Inc.

A6V10324662_g_en_US

 

201

6

-

01

-

20

Building Technologies Division

Model FDCIO422

Addressable Input/Output module

S54322-F4-A1

Installation Instructions

Download link

Desigo:

https://www.buildingtechnologies.siemens.com/extranet/ba-sp/

Download link

Cerberus PRO:

http://iknow.us009.siemens.net/infolink

INTRODUCTION

The FDCIO422 is used for the connection of up
to 2 independent Class A or 4 independent
Class B dry N/O configurable contacts. Input
lines can be supervised for open, short and
ground fault conditions (depending on EOL
termination resistor and class configuration).

Inputs can be independently configured via the
fire control panel for alarm, trouble, status or
supervisory zones.

The FDCIO422 has 4 programmable outputs
with 4 potential-free latching type form A relay
contacts for fire control installations.

Status indication per LED for each input and
output plus 1 LED for general status of the
device. Power supply via FDnet (supervised
power limited).

·

Including 4 EOL devices (470 

)

·

3 separators to separate the power limited
wiring from the non-power limited.
Separators are delivered in 3 different sizes
for standard 4

11

/

16

-inch box, 4

11

/

16

-inch

extension ring and 5-inch box (RANDL).

CAUTION

Electric shock!
High voltages may
occur on the terminals.
Always use a faceplate
and the separator(s).

Figure 1 FDCIO422 cage and carrier

CAUTION

This device is not intended for
applications in explosive environments.

Class A is equivalent to DCLA (Canada)
Class B is equivalent to DCLB (Canada)

For complete configuration and
commissioning of the FDCIO422 also refer
to the user documentation of your panel,
especially for the software tool used for
configuration.

Figure 2 Removing the cage and the terminal strips from the carrier

Summary of Contents for FDCIO422

Page 1: ...ing type form A relay contacts for fire control installations Status indication per LED for each input and output plus 1 LED for general status of the device Power supply via FDnet supervised power limited Including 4 EOL devices 470 Ω 3 separators to separate the power limited wiring from the non power limited Separators are delivered in 3 different sizes for standard 4 11 16 inch box 4 11 16 inc...

Page 2: ...se follow the corresponding description of the Panel used WIRING Refer to Figure 11 Refer to the appropriate wiring diagram and wire the addressable input output module accordingly Recommended wire size 18 AWG minimum and 14 AWG maximum Wire larger than 14 AWG can damage the connector Refer to Figures 2 and 3 Follow the instructions in the DPU manual or 8720 manual to program the FDCIO422 to the d...

Page 3: ...n power limited fire protection signaling conductors For the FDCIO422 wiring to the terminal block for line and inputs must enter the outlet box separately from the terminals for outputs For the output terminals protection with a fuse is recommended Refer to Figures 6 and 9 WIRING AT THE TERMINAL BLOCKS Minimize the length of wire entering the outlet box Figure 6 Power Limited Wiring Separators Th...

Page 4: ...se the module without the faceplate Remove the faceplate for service and maintenance reasons only Figure 7 Mounting the FDCIO422 TECHNICAL DATA Operating voltage DC 12 32 V Operating current quiescent 1 mA Absolute maximum peak current 1 92 mA Maximum current connection factor 2 4 Relays output 1 normally open normally closed DC 30 V AC 125 V Max 4x 5 A or 2x 7 A OUT B C or 1x 8 A OUT C Operating ...

Page 5: ...ptable means Insulate shields do not make any connections to the device or back box 16 Use shielded and or twisted wire to connect the switch wiring and keep the wiring as short as possible 17 Tie the switch wiring shield to the local earth ground at only one end refer to Figure 9 For multiple switches on the same input connect incoming and outgoing shields together in an acceptable means Insulate...

Page 6: ...l Remedy cause Note Any general message can be displayed together with another status Configuring the outputs Configuring the inputs For configuring the outputs proceed as follows a Determine in which position the contact is active The contact can be active when it is Closed normally open NO Open normally closed NC b After activating the contact remains Permanently active Active only for a certain...

Page 7: ...10 FDCIO422 input wiring Class A and Class B for details of Line 1 and 2 wiring see Figure 8 for details of the input wiring see Figure 11 OUT A OUT B OUT C OUT D OUT A OUT B OUT C OUT D OUT A OUT B OUT C OUT D 470 1 W Ω Rs Rp Rp please order separately ORDER NO S54312 F7 A1 100 1 W Ω ONLY OPEN MONITORING ONLY OPEN MONITORING a b a b a b a b a b a b a b a b a b a b a b a b UL864 CLASS STYLE B B UL...

Page 8: ...27 chapter EOL Devices The EOL Resistors must be connected at the end of the input lines No addressable device or 2 wire smoke detectors can be connected to the inputs ACCESSORIES DEVICE ORDER NO EOL resistor 100 Ω 1 W S54312 F7 A1 SIEMENS INDUSTRY INC 4 11 16 inch adapter plate optional M 411000 RANDL INDUSTRIES INC 5 inch Box optional T55017 RANDL INDUSTRIES INC 5 inch Box optional T55018 RANDL ...

Reviews: