Building Technologies
Control Products and Systems
FDCIO181-1 Input/Output Module
Product Manual
Characteristic
l
Microprocessor-controlled signal evaluation
l
Automatic address setting, without encoder settings or DIP switch
l
1 monitored input, 1 monitored output
l
LED display of input and output status
l
Input lines monitored for open line or short/open circuit
l
Prevention of noise interference through intelligent analysis of input signals
l
Output lines monitored for open line or short/open circuit (when potential output not
activated)
l
Output monitoring configurable(on/off)
l
Control output for equipment 24 VDC, max. 2 A
l
Communication with controller via FD18-BUS(detector line)
l
Directly used in dry areas. Applicable in dusty and humid areas when installed in FDCH221
housing
l
“Sticker Method” easy for commissioning
Application
Input
With the input a status can be monitored, the input can be configured by controller or
configuration tools as follows:
l
“
Status
“
input or
“
Alarm
“
input
l
Lead monitoring for open line or open line and short circuit
l
When inputting status, according to different status of contact, can be set as fallows:
– Normal mode: normally open NO input
– Inverted mode: normally closed NC input
Fig. 1 connection diagram of dry contact input