Periphery board (250p) FCI2016
NAC circuits
1
13 | 46
Building Technologies
A6V10315038_f_en_--
Siemens Industry, Inc.
2016-02-25
1.4.5 X304 Voice 24 V
The X304 connector on the periphery board provides the power for all Voice option
modules inside the VCA2002 Card Cage and for the connected peripherals. The cable
that connects X304 on the Periphery Board to X101 on the Card Cage is included in
the VCA2002's scope of supply.
1.4.6 X303 Battery terminal
A cable harness is required to connect batteries to the periphery board. The battery
connector end that goes on the periphery board at X303 can only connect one way
because it is keyed.
The battery connection is only made once the whole system has been configured
through jumpers and modules, and after AC has been applied.
Pin
Designation
Description
1
BAT (+)
DC 24 V feed for battery (RED WIRE)
2
BAT (-)
Return (Ground) feed for battery (BLUE WIRE)
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
The hardware required to connect the batteries to the periphery board is in the battery
kit.
1.5 NAC circuits
The periphery board has an NAC circuit that can be configured for 1 class A (style Z)
or 2 class B (style Y) circuits. Configuration is done via 3 jumpers (X604, X605 and
X606).
The NAC circuit can be configured such that, when degraded mode is active, the
NAC circuit is activated by an alarm in the case of a CPU error on the periphery
board.
For the status of degraded mode during an active alarm, NAC activation is set by the
jumpers X602 and X603.
The outputs are power limited and are supervised for short-circuit and open circuit.
They are protected against direct short-circuit of the output terminals.
The synchronization protocol is built into the panel, so no module is needed.
The NAC is configured in the Engineering tool set. This includes the output pattern and
class A/B selection. Please note that the periphery board also has three jumpers (X604,
X605 and X606) that must match the settings in the Engineering tool set. If they do not
match, a trouble will post on the system.
The end-of-line resistor is 2.4 k
Ω
, 1/2 W.
These circuits are for NAC circuits NFPA 72 Local only. For NFPA 72 Municipal Tie or
NFPA 72 Leased Line, use the leased line/city tie module FCI2020. The module
connects to X902.