Technical data
6
11 | 14
Siemens Industry, Inc.
A6V10315036_d_en_--
Building Technologies Division
2018-03-16
6 Technical data
Supply
Plug strip
X5
Voltage
DC 24 V
Special Application for strobe loads
Regulated for non-pulsing loads
Standby operating current
Max. 15 mA
Active operating current
Max. 1x class A circuit or 2x class B circuits
Max. 3 A for 1x class A circuit
Max. 3 A per class B circuit
2x 3 A = 6 A for 2x class B circuits
Outputs
Maximum circuit resistance
1.4
Ω
@ 3.0 A
Supervised for
●
Open circuit
●
Short circuit
●
Ground fault
Design
Short-circuit protection
Voltage surge protection
Power limited