Installation
Hardware components
5
28 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
5.3.5 Configurable inputs/outputs and supply voltage Vsys
The assignment of connection terminals on periphery board (2-loop) of FC722 and
periphery board (4-loop) of FC724 is not identical.
Assignment on FC722 periphery board (2-loop)
Permitted cable cross-section: 0.2 to 1.5 mm
2
.
FC722
X8
Designation
Description
6 GND_01
(–) supply output 1
DC 20 V – DC 30 V/1 A
5 VSYS_01
(+) supply output 1
4 I/O4
Configurable input/output 4
Individual current max.
300 mA
total current max. 1 A
3 I/O3
Configurable input/output 3
2 I/O2
Configurable input/output 2
1 I/O1
Configurable input/output 1
FC722
X9
Designation
Description
6 GND_02
(–) supply output 2
DC 20 V – DC 30 V/ 1 A
5 VSYS_02
(+) supply output 2
4 I/O8
Configurable input/output 8
Individual current max.
300 mA
total current max. 1 A
3 I/O7
Configurable input/output 7
2 I/O6
Configurable input/output 6
1 I/O5
Configurable input/output 5
Each of these freely configurable inputs/outputs can either be configured as an
input or output. The function and external circuit needed depend on the mode of
operation selected.
X8
X9