WL Circuit Breaker Selection and Application Guide
1
See page 85 for field install part numbers.
Characteristics table
Spring-charging motor
The spring charging motor is used to automatically charge the
breakers closing spring so the breaker is suitable for closing on
command. Motor charging is typically used for remote breaker
operation or as an alternative to local manual charging. The
motor assembly can be easily installed in the field and includes
an automatic cut-off switch which disconnects the current upon
full charge of the closing spring mechanism.
Characteristics table
Spring-
120 - 240VAC range
85 -110% of nominal
charging
24 - 240VDC range
70 - 126% of nominal
motor Power
consumption
110W
Max. charging time
10 seconds
Fuse protection rating
24-60V 6A, 120-240V 3A
(slow-blow)
Signaling
Voltage
127 - 240VAX, 24 - 125VDC
contact Continuous
current
3A
Making current
1A @24 - 125DVC, 5A @120 - 240VAC
Breaking current
1A @24 - 125DVC, 3A @120 - 240VAC
Characteristics table
Undervoltage
Operating values
85 - 110% breaker can be closed,
release UVR
35 - 70% breaker will open
120 - 240VAC
Coil voltage tolerance
85 - 110% of nominal
24 - 250VDC
Coil voltage tolerance
85 - 126% of nominal
Supply
voltage
120, 240VAC or 24, 48, 125, 250VDC
Power consumption
200VA inrush/ 5VA continuous
(same in Watts for DC)
Opening
time
of breaker
200 ms
UVR w/o time delay
(dual setting)
80 ms or 200ms
UVR with time delay
(adjustable delay)
0.2 to 3.2 sec.
Undervoltage release
In the event of loss or low level control circuit voltage, an
undervoltage release may be used to automatically open
the circuit breaker. To prevent nuisance breaker openings
from temporary voltage dips, a separate adjustable time-
delay undervoltage release is also available.
Status contact
A status contact is a mechanical switch that is suitable for
monitoring an undervoltage trip or second shut trip coil
position. The contact will be wired to the secondary contacts
of the breaker for customer connections or wired to the Breaker
Status Sensor (BSS) if communications is installed on the
breaker. Contact is 1NO configured.
WL Circuit Breaker
Factory Installed Options