background image

7  Looping Option

The following table demonstrates how the looping process reduces

the current setting of the overload by the number of times the wires

pass through the windows of the overload.

All current values are expressed in amperes.

Overload

Number

Number of Times

Current

of

Wire Passes

Range

Loops

Thru Window

Shown on label

10 - 40

0

1

Option A

5.0 - 20

1

2

Option B

3.0 - 12

2

3

Option C

2.5 - 10

3

4

Option D

2.0 - 8

4

5

Option E

1.5 - 6

5

6

Current             CT

Range

Ratio

Cat #

3UB81234JW2

100-300           300.5

2

3UB81234KW2

133-400          400.5

2

3UB81234LW2

200-600          600.5

2

3UB81234MW2

250-750          750.5

2

3UB81234NW2

400-1220

1200.5

2

# of times

wire passes

through window

for ESP200 with windows

In applications involving the use of 12 or 14 AWG wire, usually motors of

5HP or less, the wires maybe looped and passed through the windows

repeatedly before connecting to the contactor. By looping the motor

leads through the windows in the overload a second time, the overload

will read twice the current actually going to the motor. Hence the

overload can protect a motor needing half the FLA capability of the

overload. An overload with a current of 10 to 40 amperes can be used for

a motor FLA between 5 to 20 amperes. 

Similarly, motors that require only one-third, one-fourth, or one-fifth the

overload’s FLA capability can use the same size ESP200 starter by

looping three, four, or five times.

Hot Terminals

Possible cause: Loose wire connections

              Action: 

Clean connections and tighten to recommended torque.

Failure To Trip Out

Possible cause: Incorrect dial setting

              Action: 

Readjust dial setting to the FLA on the motor nameplate.

Overload Trips

Possible cause: Motor is overloaded

              Action: 

Remove cause of overload and reset overload relay.

Possible cause: Loss of phase

              Action: 

Replace burnt-out fuse, or reconnect wire in missing phase.

Possible cause: Dial setting is too low

              Action: 

Readjust dial setting to the FLA on the motor nameplate.

Possible cause: Unbalance Phase

              Action: 

Correct the power system.

Possible cause: Ground Fault

              Action: 

Fix the fault and restart.

Possible cause: Set at the wrong trip class

              Action: 

Reset the dip switches to the correct trip class.

6 Troubleshooting

3

Siemens Industry, Inc.    5300 Triangle Parkway, Norcross, GA 30092 www.usa.siemens.com

5  Reset and Test Buttons

READY

RESET

Trip Class

5

10

20

30

*

3 min.

5 min.

10 min.

15 min.

**

0.5 min.

1 min.

2 min.

3 min.

Contact Test

Device Test

(electronic functions)

NC 95 96

NO 97 98

O

O

O

O

TEST

NC 95 96

NO 97 98

RESET

NC 95 96

NO 97 98

O

O

O

O

O

O

O

O

Fig. 8

8  ESP200 wiring with External CTs

Fig. 9

ESP200

FULL  LOAD AMPS

RESET

TEST

CAT.NO.

48ATC3S00

3UBB123-4CW2

95

96

A3+

A4-      97        98

5

6

4

3

12

10

7

8

9

5

TRIP CLASS

PHASE UNBAL ON

PHASE LOSS ON

OFF
OFF

RESET MODE MAN

GROUND FAULT  ON

AUTO

OFF

10

20

30

X1

L1

X1

L2

X1

L3

Current Transformers (CT)

Note: 

Must have at least 80% of Motor amps for this test to work.

* The device must be energized with a running motor for at least the 

    minimum time, shown in the table.

** Then the test button can be pushed and held until the device trips. 

    The trip time depends on the selected Trip Class as shown in the table.

Summary of Contents for ESP200

Page 1: ...t in accordance with established safety practices b Is trained in the proper care and use of protective equipment such as rubber gloves hardhat safety glasses or faceshields flash clothing etc in accordance with established safety practices c Is trained in rendering first aid IMPORTANT THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIB...

Page 2: ...ter Size 00 4 M 2 MOTOR T2 T1 T3 CONTROL DEVICE 3 TO PILOT W V 1 L1 L2 L3 TO SUPPLY IF PROVIDED ESP200 96 95 A4 97 98 A3 GROUNDED BY CUSTOMER MAY BE OPTIONAL SEC FUSE CONTROL FUSES 1 C XF H1 H4 H3 H2 B X2 SEC X1 CONTROL TRANSFORMER OPTIONAL 96 A Fig 6 4 Terminal Connections a b A B A A Coded A B A B 1 U 0 V 2 a b c d d c B B B Assembly Removal Remote Reset Connect 24 VDC to terminal A3 and A4 Auxi...

Page 3: ...nnections and tighten to recommended torque Failure To Trip Out Possible cause Incorrect dial setting Action Readjust dial setting to the FLA on the motor nameplate Overload Trips Possible cause Motor is overloaded Action Remove cause of overload and reset overload relay Possible cause Loss of phase Action Replace burnt out fuse or reconnect wire in missing phase Possible cause Dial setting is too...

Page 4: ...e ESP200 is activated by pressing the Exterior reset button mounted on the outside of the equipment enclosure When mounting the ESP200 inside an enclosure the External reset rod must first be cut to length Allow enough space between the External reset rod and the Blue reset button so that the Blue reset button is only activated when the External reset button is depressed ...

Page 5: ...for wiring to contactors 49ASMS1 49ASMS1 How to wire for Single Phase Motor These ESP200 units below are specifically designed for single phase applications 3UB88134AB2 0 25 1 Amps 3UB88134BB2 0 75 3 4 Amps 3UB88234CW2 3 12 Amps 3UB88234DW2 5 5 22 Amps 3UB88334GW2 25 100 Amps 49ASTC1 Hazardous voltage Will cause death or serious injury To avoid electrical shock or burn turn off main and control vo...

Reviews: