Digital inputs
Definition
The motor starter has 2 digital inputs, which you can connect directly to
sensors (PNP) using 2-wire and 3-wire technology.
M12, 5-pole plug connectors are used for this.
M12, 5-pole jacks are fitted on the motor starter.
Pin assignment
The pin assignment is arranged in accordance with the standardized Y2 assi-
gnment and the examples for 2- and 3-wire circuits:
Fig. 2-8: Pin assignment with circuit examples
Attention
The digital inputs are short-circuit-proof. The current is limited to a
maximum of 200 mA. In the event of a short-circuit or overloading of the
sensor supply, the switching element (motor) and brake output are deactiva-
ted and a general fault is issued. You must acknowledge this fault with trip
reset.
Attention
Do not use an external power supply because otherwise there will be a risk
of short-circuits.
Sockets, M12, 5-pole
+
–
Out
Example:
2-wire circuit
Example:
3-wire circuit
1
4
3
2
5
+ 24 V
IN.1
IN.2
0 V
1
4
3
2
IN.1/2
+ 24 V
---
0 V
1
4
3
2
IN.2
+ 24 V
IN
1
4
3
2
0 V
+ 24 V
IN
1
4
3
2
IN.2
Summary of Contents for Ecofast 3RK1 323-2AS54-1AA0
Page 1: ...Motor Starter Manual 03 2007 ecofast Totally Integrated Automation ...
Page 2: ......
Page 12: ...ECOFAST Motor Starters viii GWA 4NEB 950 5221 12 DS 01 ...
Page 40: ...Installation of Motor Starters ECOFAST Motor Starters 3 8 GWA 4NEB 950 5221 12 DS 01 ...
Page 58: ...Device functions ECOFAST Motor Starters 6 6 GWA 4NEB 950 5221 12 DS 01 ...
Page 74: ...ECOFAST Motor Starters GWA 4NEB 950 5221 12 DS 01 ...
Page 75: ......