background image

Troubleshooting

Problem

Cause

Corrective Action

Contacts

Contacts Chatter

Low Voltage

Check supply voltage, especially during starting.

Check coil voltage rating. Increase voltage or change 

coil rating as required.

Welding

Abnormal Inrush Current

Insufficient Contact Pressure

Low Voltage Preventing Magnet 

from Sealing

Foreign Matter Preventing 

Contacts from Closing

Short Circuit

Excessive Inrush Current

Check for grounds, shorts, or excessive load current.

Replace contacts and springs, check contacts for 

abnormal wear or damage.

Check supply voltage to coil, especially for momentary 

dip during startup.

Clean contacts with LPS CFC-Free Electro Contact 

Cleaner. Contacts used at low current and voltage 

should be cleaned with Freon.

Remove fault and check to be sure fuse or breaker 

size is correct.

Use next larger size contactor.

Short Contact Life or 

Overheating

Filing or Dressing

Interrupting Excessively High 

Currents

Weak Contact Pressure

Foreign Matter on Contact 

Surface

Short Circuit or Ground Fault

Loose Connection in Power 

Circuit

DO NOT FILE SILVER CONTACTS

. Rough spots or 

discoloration will not harm contacts of impair their 

efficiency.

Check for grounds, shorts or excessive currents.

Use larger size contactor.

Replace contacts and springs, check contacts for 

abnormal wear or damage.

Clean contacts with LPS CFC-Free Electro Contact 

Cleaner. Take steps to reduce entry of foreign matter 

into enclosure.

Remove fault and check to be sure fuse or breaker 

size is correct.

Clean and tighten.

Coils

Open Circuit

Overheated Coil

Mechanical Damage

Incorrect Coil

Caution -

All control wiring for contactor operation must only be 

made to the coil isolation contact terminals #2 and #3, 

and L2 terminal connection points. Wiring made to any 

other terminals will burn out the coil and diode. If a coil 

burnout occurs, both the coil and diode must be 

replaced.

Replace with new coil. Handle and store new coils 

carefully.

Check coil rating and replace with correct coil.

Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092      

A5E31166447A-002

Troubleshooting continued

Problem

Cause

Corrective Action

Magnetic and 

Mechanical Parts

Each CLM contactor has an electronic control module 

‘CLMKCMR’ which is used to energize and close the 

contactor and for the release circuit. It is designed for 

short time actuation of 1-3 cycles only. All coils are 

designed with a small wattage resistor in addition to a 

diode at coil voltage higher than 120 Volts. Remote 

solid state switching devices have ‘off state’ leakage 

currents. They may also pass utility transient voltages 

through to the device electronics. The low level ‘off 

state’ voltages are insufficient to actuate the contactor 

but large enough to burn out the resistors. Normal 

actuating voltages are quickly disconnected from the 

coils and control module by the latch clearing contacts. 

Coil and module failures are possible when used with 

solid state relays and PLC outputs. 24-Volt systems 

are ok to use, but 120 volts and above should be 

discouraged. If higher voltages cannot be avoided, an 

interposing relay should be used.

Failure to Pick-up and 

Seal

Failure to Drop-Out

Low Voltage

Wrong Coil or 

Wrong Connection

Mechanical Obstruction

Coil Open or Overheated

Sticky Substance on Pole 

Faces

Release Coil not Energized

Worn or Rusted Parts Causing 

Binding

Contacts Welded

Check system voltage and voltage dips during starting.

Check coil marking and wiring.

With power off, check for movement of armature and 

contacts.

Replace.

Clean pole faces with LPS CFC-Free Electro Contact 

Cleaner.

Check coil, coil circuit or length of leads from supply 

voltage to coil. Coil may be open or lead length is 

excessive.

Replace unit.

See ‘Welding’ under Contacts.

These instructions do not purport to cover all details or 
variations in equipment nor to provide for possible con-
tingency to be met in connection with installation, op-
eration, or maintenance. Should further information be 
desired, or should problems arise which are not cov-

ered sufficiently for the purchaser’s purpose, the matter 

should be referred to the local SIemens Industry, Inc., 

Sales Office.

The contents of this instruction sheet shall not become 
part of or modify any prior or existing agreement, com-
mitment or relationship. The sales contract contains the 
entire obligation of Siemens Industry, Inc. The warranty 
contained in the contract between the parties is the sole 
warranty of Siemens Industry, Inc. Any statements con-
tained herein do not create new warranties or modify the 
existing warranty.

Magnetic and  

Mechanical Parts

Contacts

Summary of Contents for E87010-A0104-T003-A6-CLM0

Page 1: ...age and current rating for various loads Each contactor and its associated load should be protected against short circuits by a suitable branch circuit pro tective device selected in accordance with the National Electric Code NEC Description AC Coil Data Poles Inrush VA Dropout VA 2 4 410 40 5 410 40 Care should be taken when servicing that leads do not be come changed from their factory installed...

Page 2: ...leads to be handled are de energized With power off operate contactors relays and interlocks to see that they work freely See that all terminals and current carrying connections are clean and tight For electrical connection wire per one of the schematics shown in Fig 2 thru 4 depending on the desired control Magnetically latched contactors are equipped with coils designed for intermittent duty onl...

Page 3: ... the crossbar Contact Inspection refer to Figure 1 Loosen the two arc chute screws 6 located immediately above and below the nameplate and remove the arc chute 7 The contacts 8 are visible Re tighten the screws per Table 2 Contact Wear and Replacement refer to Figure 1 Table 4 CAUTION Install arcbox prior to energization Contacts are designed for a long service life based on a spe cific electrical...

Page 4: ...Hand Off Auto Control Fig 5 Dimension Drawing 30 Amp Device VOLTAGE CONTROL L1 L2 ON OFF BLACK AC AC L2 RED WHITE CLMFCCK11 3 2 RED CLMFCAK11 OFF ON RED CR REMOTE DEVICE CR CR CLM CONTACTOR VOLTAGE CONTROL ON OFF BLACK AC AC L2 RED WHITE CLMFCCK11 3 2 RED ON OFF RED CR REMOTE CR CR L1 1 L2 X2 H A O DEVICE SELECTOR SWITCH CLM CONTACTOR ...

Page 5: ... protect the equipment against dust moisture and falling objects Apparatus stored for long periods may corrode Damage while stored will be minimized by maintaining the best possible storage conditions and by periodically inspect ing the equipment and arresting the progress of corro sion and other forms of deterioration which may be found A small amount of heat will stop corrosion that occurs from ...

Page 6: ...c control module CLMKCMR which is used to energize and close the contactor and for the release circuit It is designed for short time actuation of 1 3 cycles only All coils are designed with a small wattage resistor in addition to a diode at coil voltage higher than 120 Volts Remote solid state switching devices have off state leakage currents They may also pass utility transient voltages through t...

Reviews: