background image

Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092      

A5E31166447A-002

Power Circuit Terminals

Wire Size #14 AWG 

-

#8 AWG

Wire with copper conductors only, unless terminals are 

marked “AL-CU”

(Wire with conductors rated 75 

°C

. If conductors rated 

higher than 75 

°C

are used, their size must be based on 

the ampacity values for 75 

°C

conductors. Terminal 

torque values are shown in Table 2.)

Installation - Be sure power is off

The  nameplate  ratings  of  the  contactor  must  agree  with  the 

power supply and the rating of the load. Contactor mounting 

should be solid to prevent vibration. When the contactor is 

provided with a channel iron base, grout the base in place. 

The preferred and recommended mounting position of the con

-

tactor is in a vertical plane. Before making any connections, 

be certain that all leads to be handled are de-energized. With 

power off, operate contactors, relays and interlocks to see that 

they  work  freely.  See  that  all  terminals  and  current  carrying 

connections are clean and tight. For electrical connection, wire 

per one of the schematics shown in Fig. 2 thru 4 depending on 

the desired control.

(Magnetically-latched contactors are equipped with coils 

designed for intermittent duty only. Faulty coil action can 

be caused by a defective coil or damaged control module. 

Replacement of both is recommended when the contactor 

will not pull in or drop out. Coil replacement for the purpose of 

changing the control voltage rating does not require auxiliary 

contact or control module replacement.)

Table 2 - Torque
Location (Qty.)

Driving Torque 

(lb.-in.)

Figure 1 

Item

Cover Screw (2)

8-9

6

Coil Wire Connector (2)

8-9

12

Stationary Contact Screw (2/pole)

8-9

10

Main Power Connector (2/pole)

18-20

13

Fig. 1

CAUTION:

 Avoid attempting to manually latch or delatch the contactor.

6

12

13

10

11

5

8

9

1

2

3

4

7

Summary of Contents for E87010-A0104-T003-A6-CLM0

Page 1: ...age and current rating for various loads Each contactor and its associated load should be protected against short circuits by a suitable branch circuit pro tective device selected in accordance with the National Electric Code NEC Description AC Coil Data Poles Inrush VA Dropout VA 2 4 410 40 5 410 40 Care should be taken when servicing that leads do not be come changed from their factory installed...

Page 2: ...leads to be handled are de energized With power off operate contactors relays and interlocks to see that they work freely See that all terminals and current carrying connections are clean and tight For electrical connection wire per one of the schematics shown in Fig 2 thru 4 depending on the desired control Magnetically latched contactors are equipped with coils designed for intermittent duty onl...

Page 3: ... the crossbar Contact Inspection refer to Figure 1 Loosen the two arc chute screws 6 located immediately above and below the nameplate and remove the arc chute 7 The contacts 8 are visible Re tighten the screws per Table 2 Contact Wear and Replacement refer to Figure 1 Table 4 CAUTION Install arcbox prior to energization Contacts are designed for a long service life based on a spe cific electrical...

Page 4: ...Hand Off Auto Control Fig 5 Dimension Drawing 30 Amp Device VOLTAGE CONTROL L1 L2 ON OFF BLACK AC AC L2 RED WHITE CLMFCCK11 3 2 RED CLMFCAK11 OFF ON RED CR REMOTE DEVICE CR CR CLM CONTACTOR VOLTAGE CONTROL ON OFF BLACK AC AC L2 RED WHITE CLMFCCK11 3 2 RED ON OFF RED CR REMOTE CR CR L1 1 L2 X2 H A O DEVICE SELECTOR SWITCH CLM CONTACTOR ...

Page 5: ... protect the equipment against dust moisture and falling objects Apparatus stored for long periods may corrode Damage while stored will be minimized by maintaining the best possible storage conditions and by periodically inspect ing the equipment and arresting the progress of corro sion and other forms of deterioration which may be found A small amount of heat will stop corrosion that occurs from ...

Page 6: ...c control module CLMKCMR which is used to energize and close the contactor and for the release circuit It is designed for short time actuation of 1 3 cycles only All coils are designed with a small wattage resistor in addition to a diode at coil voltage higher than 120 Volts Remote solid state switching devices have off state leakage currents They may also pass utility transient voltages through t...

Reviews: