Operation and Display
4.3 Key Definition
SICAM P27, 3-phase Harmonic Power Meter, User Manual
E50417-H8940-C560-
, Release Date
29
2. Data items configurable with key (Note 1)
NO.
1
st
level menu
2
nd
level menu
Symbol
Definition
Symbol
Definition
Range
Remarks
1
Communi-
cation
setting
Baud rate
600 ... 38400
Default setting:
2400
Parity
8E1/8o1/8n1/8n
2
Default setting: 8E1
Modbus address
0 ... 247
Default setting: 0
Modbus sending
delay
0 ... 2999
Unit: ms
Default setting: 10
DL/T645 high 6
address
0 ... 999999
Default setting: 0
DL/T645 low 6
address
0 ... 999999
Default setting:
Last 3 digital of S/N
2
Ratio
setting
(Note 2)
Voltage ratio
integer
0 ... 9999
Combination 0 ...
9999.9999
Default setting: 1
Voltage ratio
decimal part
0 ... 9999
Current ratio
integer part
0 ... 9999
Combination 0 ...
9999.9999
Default setting: 1
Current ratio
decimal part
0 ... 9999
3
System
setting
Wiring mode
3P4L
3P3L_2CT
3P3L_3CT
AUto
3phase4wire
3phase3wire -2CT
3phase3wire -3CT
auto
Password
6 bits in total, Set
L0-2 password
Default setting:
000000
4
Clearing
extreme
value
Meter reset