Data Exchange Between the DP Master and AS-i Slave
57
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
Table 2-2
Parameters for Sending/Receiving
DP-V1
SIMATIC S7 (SFC 58/59)
For PC: DP programming
interface (dpc*_read/write)
Meaning
PROFIBUS
address
LADDR
(the start address of the
cyclic input bytes of the
DP/AS-i Link must be
specified (see also Section
1.9). The S7 CPU calculates
the PROFIBUS address from
this information.)
C_Ref
PROFIBUS address of the
DP/AS-i Link (DP slave)
IOID
The following fixed value
must be entered: B#16#54
–
Fixed value
Slot_number
Is calculated from LADDR;
Not an SFC parameter
Slot_number
With DP/AS-i Link:
Any value
Index
RECNUM
Index
Data record number
(140–147; see Table 2-3)
Length
RECORD
Referenced using ANY
pointer
Length_s
Length of the input/output
data area
Data
RECORD
Referenced using ANY
pointer
Data_s
Address of the input/output
data area
RET_VAL
BUSY
Return parameter for
execution check
You will find sample programs for SIMATIC S7 in Section 2.4.3
Summary of Contents for DP/AS-Interface Link 20E
Page 6: ...Preface 6 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Page 10: ...Contents 10 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Page 124: ...Using the Command Interface 124 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Page 132: ...Slave Diagnostics 132 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Page 150: ...Notes on the CE Mark 150 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...