RXZ90.1 – Receiver with PPS2 interface 

CA2N1644en 

Building Automation 

 

07.2001 

Connection terminals 

Connecting a commissioning and service tool or service terminal to the tool socket 
on the receiver provides access to the connected room controllers.  

The bus cable is looped through to the tool socket for this purpose. The bus cable is 
not affected by the receiver. 
The PPS2 interface is also routed to the tool socket, enabling a service terminal to 
be connected. 

 

8

7

6

5

4

3

2

1

C–

C+

CP–

CP+

80085

 

PPS2 interface, power supply 

CP+ 

Device power supply, PPS2 data (positive) 

CP– 

Device power supply, PPS2 data (negative) 

Bus connection (looped to tool socket) 

C+ 

with LON bus (DESIGO RXC): CLA 

C– 

with LON bus (DESIGO RXC): CLB 

 

  5...8 

Not used 

 

Tool socket 

Standard RJ45 tool socket 
 

 

Communication 

Diagnostic plug 

1

3206Z01

2 3 4 5 6 7 8

 

1  with LON bus (DESIGO RXC): CLA 
2  with LON bus (DESIGO RXC): CLB 
3   
4   
5   
6   

CP+  

PPS2 data 

CP–  

PPS2 data 

 
 

Button for installation 
Button for installation 
Red LED + 
Red LED – 
Green LED + 
Green LED – 

 

Connection diagrams 

Connecting the receiver to a DESIGO RXC room controller: 

 

00476

PPS2

Tool

A

R1

B

4

3 1 2

4 3 2

1

C–

C+

CP–

CP+

N1

CP+

CP

CLA

CLB

LON-Bus

PPS2

7

8

6 5

C

Twisted pair 

 
 

R1 RXZ90.1 receiver 
N1 RXC… room controller 
A Connection for RXT10.1 commissioning and service tool 
B Connection for RXT20.1 service terminal with PPS2 interface 
C Connection for diagnostic plug 

 

Summary of Contents for DESIGO RX Series

Page 1: ...unction with the QAX90 1 QAX91 1 wireless room units data sheet CA2N1643 Determines the average room temperature from several room units PPS2 interface to room controller Socket for commissioning and service tool diagnostic plug or service terminal Use The RXZ90 1 is used for wireless reception of the room temperature from the QAX90 1 and the room temperature setpoint from the QAX91 1 and for tran...

Page 2: ... the average of the temperature values received The average room temperature is then transmitted to the room controller In the case of room units with setpoint adjusters QAX91 1 only one may be assigned to each receiver Other room units with setpoint adjusters are treated as QAX90 1 units room temperature only QAX91 1 QAX90 1 QAX90 1 RXZ90 1 QAX90 1 QAX90 1 00481 868 MHz Design The receiver is des...

Page 3: ... cover The unit must be mounted at least 1 metre from the transmitter An error signal sensor short circuit is transmitted after 3 years of uninterrupted operation battery monitoring feature The batteries of all room units must then be replaced à N B The plant documentation must contain a note to this effect Mounting instructions The receiver is suitable for mounting on walls or ceilings and for in...

Page 4: ...to the battery holder of the room unit allows you to check the wireless link with the room controller After receiving this signal the receiver will close the PPS2 interface for 1 5 s This briefly extinguishes the display on the connected RXT20 1 service terminal or the green LED on the diagnostic plug see Diagnostics below If there is no wireless link with the receiver the display on the service t...

Page 5: ... receiver starts in installation mode when the power supply is connected It scans for installation signals for 3 minutes and identifies all room units in installation mode within its receiver range The first 5 room units identified are entered in the device list of the receiver For each receiver a delay must precede the process of establishing communication as the receiver can also pick up signals...

Page 6: ...R 11 2k 4 3 2 1 7 8 6 5 00495 LEDs 2mA Button 2x green 1x red RJ45 telephone type socket Cable 8 wire Green LED 2mA Green LED Optional lights up in event of incorrect polarity Red LED Pushbutton Status Red LED signals Installation mode Permanently ON Normal mode Receiver s device list is empty Rapid flashing approx 5 times per s Normal mode Receiver s device list not empty 1 room unit 1 flash 5 s ...

Page 7: ...ing Technologies RXZ90 1 Receiver with PPS2 interface CA2N1644en Building Automation 07 2001 Sustained pressure 5s Deletes the device list from the receiver and then brings it to the Normal mode with an empty device list ...

Page 8: ...lengths Receiver Room controller See controller installation principles for DESIGO RXC see CA2Z3802 Cable type 4 core twisted pair unscreened Tool connecting cable Made up in house max 3 m Housing protection standard Protection standard to EN 60529 IP 30 Protection class Insulation protection class III Ambient conditions Ambient conditions to IEC721 Operation Transport Environmental conditions Cla...

Page 9: ...CP 2 Device power supply PPS2 data negative Bus connection looped to tool socket C 3 with LON bus DESIGO RXC CLA C 4 with LON bus DESIGO RXC CLB 5 8 Not used Tool socket Standard RJ45 tool socket Communication Diagnostic plug 1 3206Z01 234 5678 1 with LON bus DESIGO RXC CLA 2 with LON bus DESIGO RXC CLB 3 4 5 6 7 CP PPS2 data 8 CP PPS2 data Button for installation Button for installation Red LED R...

Page 10: ...10 11 Siemens Building Technologies RXZ90 1 Receiver with PPS2 interface CA2N1644en Building Automation 07 2001 Dimensions 9 5 32 36 4 2 60 00496 90 100 56 60 56 ...

Page 11: ...11 11 Siemens Building Technologies RXZ90 1 Receiver with PPS2 interface CA2N1644en Building Automation 07 2001 2001 Siemens Building Technologies Ltd Subject to technical alteration ...

Reviews: