3/11 

Siemens Building Technologies 

RXZ90.1 – Receiver with PPS2 interface 

CA2N1644en 

Building Automation 

 

07.2001 

 

 
 
 
 
 
 

Mounting plate 

 
 
 
 

Housing 

00477

 

 

 
 
 

RJ45 socket on base of unit for: 

• 

RXT10.1 commissioning and 
service tool 

• 

RXT20.1 service terminal 

• 

Diagnostic plug, with button 
for LON registration 

 

80084

 

Disposal 

The unit contains electric and electronic components and must not be disposed of 
with domestic waste.  

The local and actual regulations must be observed. 

Engineering notes 

• 

The receiver receives its power via the PPS2 interface 

• 

Receiver range: approx. 30 m, and up to 100 m in the open. The range can vary 
widely. Room topologies and building materials (metal, concrete etc.) reduce or 
alter the range significantly. 

• 

To ensure good wireless communication with the room units, avoid metal 
obstacles in the wireless field.  

à

 Avoid mounting the unit on or behind a metal cover!

 

• 

The unit must be mounted at least 1 metre from the transmitter 

• 

An error signal "sensor short circuit" is transmitted after 3 years of uninterrupted 
operation (battery monitoring feature) The batteries of 

all

 room units must then be 

replaced. 

à

 N.B.: The plant documentation must contain a note to this effect! 

Mounting instructions 

• 

The receiver is suitable for mounting on walls or ceilings, and for installation in a 
flush mounting box 

• 

An elevated position, or mounting on the same storey as the room unit(s) can 
extend the wireless range 

• 

Depending on the materials used for the ceiling, the receiver may be concealed in 
the ceiling void  
(note that metal must be avoided) 

• 

The admissible ambient conditions must be observed 

• 

The mounting instructions and a drilling template are printed on the device packa-
ging 

• 

A set of fixing accessories is enclosed with the room unit 

 

• 

Do not mount on a metal surface 

• 

Do not install behind a cover or a metal grid which impedes wireless 
communication 

• 

The unit must be mounted at least 1 metre from the transmitter 

 

 

STOP

 

Caution! 

Summary of Contents for DESIGO RX Series

Page 1: ...unction with the QAX90 1 QAX91 1 wireless room units data sheet CA2N1643 Determines the average room temperature from several room units PPS2 interface to room controller Socket for commissioning and service tool diagnostic plug or service terminal Use The RXZ90 1 is used for wireless reception of the room temperature from the QAX90 1 and the room temperature setpoint from the QAX91 1 and for tran...

Page 2: ... the average of the temperature values received The average room temperature is then transmitted to the room controller In the case of room units with setpoint adjusters QAX91 1 only one may be assigned to each receiver Other room units with setpoint adjusters are treated as QAX90 1 units room temperature only QAX91 1 QAX90 1 QAX90 1 RXZ90 1 QAX90 1 QAX90 1 00481 868 MHz Design The receiver is des...

Page 3: ... cover The unit must be mounted at least 1 metre from the transmitter An error signal sensor short circuit is transmitted after 3 years of uninterrupted operation battery monitoring feature The batteries of all room units must then be replaced à N B The plant documentation must contain a note to this effect Mounting instructions The receiver is suitable for mounting on walls or ceilings and for in...

Page 4: ...to the battery holder of the room unit allows you to check the wireless link with the room controller After receiving this signal the receiver will close the PPS2 interface for 1 5 s This briefly extinguishes the display on the connected RXT20 1 service terminal or the green LED on the diagnostic plug see Diagnostics below If there is no wireless link with the receiver the display on the service t...

Page 5: ... receiver starts in installation mode when the power supply is connected It scans for installation signals for 3 minutes and identifies all room units in installation mode within its receiver range The first 5 room units identified are entered in the device list of the receiver For each receiver a delay must precede the process of establishing communication as the receiver can also pick up signals...

Page 6: ...R 11 2k 4 3 2 1 7 8 6 5 00495 LEDs 2mA Button 2x green 1x red RJ45 telephone type socket Cable 8 wire Green LED 2mA Green LED Optional lights up in event of incorrect polarity Red LED Pushbutton Status Red LED signals Installation mode Permanently ON Normal mode Receiver s device list is empty Rapid flashing approx 5 times per s Normal mode Receiver s device list not empty 1 room unit 1 flash 5 s ...

Page 7: ...ing Technologies RXZ90 1 Receiver with PPS2 interface CA2N1644en Building Automation 07 2001 Sustained pressure 5s Deletes the device list from the receiver and then brings it to the Normal mode with an empty device list ...

Page 8: ...lengths Receiver Room controller See controller installation principles for DESIGO RXC see CA2Z3802 Cable type 4 core twisted pair unscreened Tool connecting cable Made up in house max 3 m Housing protection standard Protection standard to EN 60529 IP 30 Protection class Insulation protection class III Ambient conditions Ambient conditions to IEC721 Operation Transport Environmental conditions Cla...

Page 9: ...CP 2 Device power supply PPS2 data negative Bus connection looped to tool socket C 3 with LON bus DESIGO RXC CLA C 4 with LON bus DESIGO RXC CLB 5 8 Not used Tool socket Standard RJ45 tool socket Communication Diagnostic plug 1 3206Z01 234 5678 1 with LON bus DESIGO RXC CLA 2 with LON bus DESIGO RXC CLB 3 4 5 6 7 CP PPS2 data 8 CP PPS2 data Button for installation Button for installation Red LED R...

Page 10: ...10 11 Siemens Building Technologies RXZ90 1 Receiver with PPS2 interface CA2N1644en Building Automation 07 2001 Dimensions 9 5 32 36 4 2 60 00496 90 100 56 60 56 ...

Page 11: ...11 11 Siemens Building Technologies RXZ90 1 Receiver with PPS2 interface CA2N1644en Building Automation 07 2001 2001 Siemens Building Technologies Ltd Subject to technical alteration ...

Reviews: