background image

    


Siemens Schweiz AG 

 

A6V11646020_en--_b 

Smart Infrastructure 

 

2020-07-10 

  

Technical data 

  

Power supply 

 

Operating voltage (24 V~, 

AC 24 V -15 / +20 % (SELV / PELV) or 
AC 24 V Class 2 (US) 
48…63 Hz 

Functional ground (US) 
Functional earth 

  

The terminal for the functional ground must be 

connected on the installation side with the building 

grounding system (PE). 

Screw terminals for wire cross sections up to 

Max. 2.5 mm

2

 (14 AWG) 

Internal fusing 

3.15 A irreversible / non-replaceable 

External supply line fusing (EU) 

Non-renewable fuse max. 10 A slow-blow 

 or  

circuit breaker max. 13 A 

Tripping characteristic B, C, D per EN 60898 

 or 

Power supply with current limitation of max. 10 A 

 

 

  

Power consumption (for transformer planning) 

 

Base load 

With M-Bus, with KNX 

12 VA / 0.5 A  

19 VA / 0.8 A 

 

 

  

Function data 

 

Hardware information 
Processor 

NXP i.MX8 DualX 

Storage 

1 GByte RAM 

8 GByte eMMC 

 

 

 

Data backup in the event of power failure 
Energy reserve (Supercap) to support real-time clock (7 days). 
Energy reserve can be extended to min. 1 month using optional battery CR2032  

(Battery safety requirement and specification for CR2032 according to IEC 60086-4 or UL1642. 

Battery must be rated for ambient temperature 70 °C (158 °F)) 
Data available if stored to flash memory. Occurs every 5 minutes. 

 

 

  

Interfaces 

 

Ethernet interface 
Plug 

2 x RJ45, shielded 

Interface type 

10Base-T / 100Base-TX, IEEE 802.3 compatible 

Bit rate 

10/100 Mbps, autosensing 

Protocol 

BACnet on UDP/IP and HTTPS on TCP/IP 

Cabling (in-house cabling only), cable type 

10 Mbps: Min. CAT3, shielded cable is recommended 

100 Mbps: Min. CAT5, shielded cable is recommended 

Cable length 

Max. 100 m (330 ft) 

 

 

 

Screw terminals, plug-in 
Cu-wire or Cu-strand with wire end sleeve 

1 x 0.6 mm ∅ to 2.5 mm

2

 (22 to 14 AWG) 

or 2 x 0.6 mm ∅ to 1.0 mm

2

 (22 to 18 AWG) 

Cu-strand without wire end sleeve 

1 x 0.6 mm ∅ to 2.5 mm

2

 (22 to 14 AWG) 

or 2 x 0.6 mm ∅ to 1.5 mm

2

 (22 to 16 AWG) 

Summary of Contents for Desigo PXC5.E003

Page 1: ...BACnet MS TP and Modbus devices Communication BACnet IP 2 port Ethernet switch for low cost cabling Integration of Modbus data points via RTU and or TCP Integration of BACnet MS TP devices WLAN interface for engineering and commissioning Operating voltage AC 24 V Mounted on standard rails or on the wall Plug in screw terminal blocks ...

Page 2: ...et communication on IP or MS TP in compliance with the BACnet standard including B BC profile Rev 1 15 Wireless connection for engineering and commissioning Cloud connectivity for remote access Integration of Modbus data points via RTU and or TCP Type summary Type Order number Description PXC5 E003 S55375 C103 System controller to integrate up to 500 Modbus data points via RTU and or TCP up to 30 ...

Page 3: ...using 14 Holes for wall mounting 2 Front cover 15 Date Series and Serial number 3 LEDs for communication and state 16 QR code for default WLAN access Description see Technical data LED displays Activity LED Color Activity Function Ethernet 1 2 Green Continuously ON Continuously OFF Flashing Link active No connection Network traffic Yellow Continuously ON Continuously OFF Link 100 Mbps Link 10 Mbps...

Page 4: ... no client is connected As per description Do the following to reset the device to factory state 1 Power off the device 2 Power on the device 3 Wait until all LEDs light up and turn off again then press the Service button 4 Keep the Service button pressed until all LEDs light up then release the button All LEDs go off the device restarts 5 Wait until the device has fully started unconfigured green...

Page 5: ... a flat surface Plug in screw terminals connect power and interfaces Ambient temperature 5 50 C 23 122 F Ambient temperature 5 45 C 23 113 F Wall horizontal From left to right From right to left Overhead Wall vertically From top to bottom From bottom to top On a horizontal surface CAUTION Risk of overheating for failure to comply with ambient temperature Burning and damage to the device Ensure suf...

Page 6: ... GByte RAM 8 GByte eMMC Data backup in the event of power failure Energy reserve Supercap to support real time clock 7 days Energy reserve can be extended to min 1 month using optional battery CR2032 Battery safety requirement and specification for CR2032 according to IEC 60086 4 or UL1642 Battery must be rated for ambient temperature 70 C 158 F Data available if stored to flash memory Occurs ever...

Page 7: ...hable with DIP switch Internal bus polarization 270 Ohm pull up pull down resistances switchable with DIP switch Cabling in house cabling only Distance between 2 devices Length of the MS TP line 3 wire cable shielded Max 500 m 1650 ft Max 1000 m 3300 ft Protection Short circuit proof Protection against faulty wiring with AC 24 V WLAN interface Interface type Wireless access point Supported standar...

Page 8: ... UL cUL approbation US Canada UL916 http ul com database CSA certification C22 2 http csagroup org services industries product listing FCC CFR 47 Part 15 Class B BACnet B BC Environmental compatibility 1 The product environmental declaration 1 contains data on environmentally compatible product design and assessments RoHS compliance materials composition packaging environmental benefit disposal 1 ...

Page 9: ...ion is subject to the following two conditions 1 This device may not cause interference and 2 this device must accept any interference received including interference that may cause undesired operation Radio frequency radiation exposure Information for USA and Canada This equipment complies with FCC and IC radiation exposure limits set forth for an uncontrolled environment This equipment should be...

Page 10: ...nation Polar On off Switch for polarization 65 66 67 COM1 Interface EIA 485 Modbus MS TP 68 69 70 COM2 71 72 MBUS M bus interface for future use Warranty Technical data on specific applications are valid only together with Siemens products listed under Equipment combinations Siemens rejects any and all warranties in the event that third party products are used ...

Page 11: ..._b Smart Infrastructure 2020 07 10 Dimensions All dimensions in mm and inches 124 4 88 117 4 61 110 4 33 129 5 08 4 1 0 1 6 144 5 67 26 5 1 04 45 1 77 65 5 2 58 70 5 2 78 4 0 16 21 5 0 85 11 0 43 45 1 77 21 5 0 85 11 0 43 35 5 1 40 49 1 91 ...

Page 12: ...itzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH 6300 Zug Tel 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2020 Technical specifications and availability subject to change without notice Document ID A6V11646020_en _b Edition 2020 07 10 ...

Reviews: