ASI FAIL
(Yellow)
Normally OFF. When illuminated, indicates
that the ASI communication has
terminated.
CPC-DAC FAIL
(Yellow)
Normally OFF. When illuminated, indicates
that the communication between PMI/PMI-
2/PMI-3 and DAC-NET has terminated.
ALARM
(Red)
Normally OFF. When illuminated, indicates
that the DAC-NET has detected an active
alarm.
EXT ALARM TRBL (Yellow)
Normally OFF. When illuminated, indicates
that the DAC-NET has detected a trouble
on the External Alarm input (open circuit or
short circuit).
D-NET
TRBL
_
MAIN IN
(Yellow)
Normally OFF. When illuminated, indicates
RETURN OUT
that the DAC-NET has detected a trouble
on Main In.
GND FAULT
(Yellow)
Normally OFF. When illuminated, indicates
that the DAC-NET has detected a ground
fault on one of its field wires before the
node.
TRBL
_
MAIN OUT
(Yellow)
Normally OFF. When illuminated, indicates
RETURN IN
that the DAC-NET has detected a trouble
on Main Out. When blinking twice per
second, indicates that the DAC-NET has
detected a trouble on Return In (open
circuit, short circuit or data trouble).
GND FAULT
(Yellow)
Normally OFF. When illuminated, indicates
that the DAC-NET has detected a ground
fault on one of its field wires after the
node.