Product overview
2.3 Firmware functions
CPU 1518HF-4 PN (6ES7518-4JP00-0AB0)
14
Equipment Manual, 05/2021, A5E49868646-AA
2.3
Firmware functions
Functions
CPU 1518HF-4 PN supports the following firmware functions:
Function
Description
Additional information
CPU redundancy
There are two duplicate CPUs that synchronize their
data via two duplex fiber-optic cables, which connect
the CPUs directly to each other via plug-in synchroniza-
tion modules. If one of the CPUs fails, the other CPU
retains control of the process.
Redundant System S7-1500R/H
https://support.industry.siemens.co
) Sys-
tem Manual
Safety Integrated
The integrated F-functionality processes standard and
safety programs.
This allows fail-safe data to be evaluated in the standard
user program. As a result of the integration, the system
advantages and the extensive functionality of SIMATIC
are also available for fail-safe applications.
The F-CPU is certified for use in safety mode up to:
•
Safety Integrity Level SIL3 acc. to IEC 61508
•
Performance Level (PL) e and Category 4 according
to ISO 13849-1:2006 or according to EN ISO 13849-
1
Additional password protection for F-configuration and
F-program is set up for IT security.
SIMATIC Safety - Configuring and
Programming
https://support.industry.siemens.co
) pro-
gramming and operating manual
Integrated system diag-
nostics
The system automatically generates the messages for
the system diagnostics and outputs these messages via
a programming device/PC, HMI device or the integrated
display. System diagnostics information is also available
when the CPUs are in operating state STOP.
Function manual Diagnostics
https://support.industry.siemens.co
Integrated trace func-
tionality
Trace functionality supports you in troubleshooting
and/or optimizing the user program.
You record device tags and evaluate the recordings with
the trace and logic analyzer function. Tags are, for ex-
ample, drive parameters or system and user tags of a
CPU.
Trace and logic analyzer functions are suitable for moni-
toring highly dynamic processes.
Note: Note that the S7-1500R/H redundant system
supports recording of measurements. However, saving
the measurements to the SIMATIC memory card is not
supported.
Function manual Using the trace and
logic analyzer function
Summary of Contents for CPU 1518HF-4 PN