Description of the device
1.3 PROFIBUS interface
CP 5613 A3 / CP 5614 A3
12
Operating Instructions, 10/2012, C79000-G8976-C277-01
PROFIBUS network
The physical link between the PROFIBUS interface and the PROFIBUS network is via a
floating RS-485 interface that is part of the module. Depending on the network configuration,
data rates of 9.6 Kbps up to a maximum of 12 Mbps are possible in the PROFIBUS network.
Note
You will find information about the structure of a PROFIBUS network in the system manual
"PROFIBUS Network Manual". The document is part of the Manual Collection. You will also
find this on the Product Support pages under the following entry ID:
35222591 (
http://support.automation.siemens.com/WW/view/en/35222591
)
PIN assignment
The D-sub female connector has the following pin assignment:
5 4 3 2 1
9 8 7 6
PIN
Short name
Meaning
Input/output
1
NC
Socket pin 1 is not connected.
-
2
NC (M24)
Socket pin 2 is not connected. With other MPI/DP components,
the return line of the floating 24 V power supply may be via this
pin.
-
3
LTG_B
Signal line B of the PROFIBUS connector.
Input/output
4
RTSAS
RTSAS, input signal for direct MPI link. The control signal is "1"
active when the automation system connected over a special
MPI cable is sending.
Input
5
M5EXT
M5EXT return line (GND) of the 5 V power supply. The current
load of an external consumer connected between P5EXT and
M5EXT must not exceed a maximum of 90 mA.
Output
6
P5EXT
P5EXT supply (+5 V) of the 5 V power supply. The current load
of an external consumer connected between P5EXT and
M5EXT must not exceed a maximum of 90 mA (short-circuit
proof).
Output
7
NC (P24V)
Socket pin 7 is not connected. With other MPI/DP components,
the P24V supply of the floating 24 V power supply may be via
this pin.
-
8
LTG_A
Signal line A of the PROFIBUS connector.
Input/output
9
RTS
RTS output signal of the CP module. The control signal is "1"
active when the device (PG or PC) is sending.
Output
Shield
The shield is connected to components of the connector
housing.
Summary of Contents for CP 5613 A3
Page 6: ...Preface CP 5613 A3 CP 5614 A3 6 Operating Instructions 10 2012 C79000 G8976 C277 01 ...
Page 8: ...Table of contents CP 5613 A3 CP 5614 A3 8 Operating Instructions 10 2012 C79000 G8976 C277 01 ...
Page 22: ...Configuration CP 5613 A3 CP 5614 A3 22 Operating Instructions 10 2012 C79000 G8976 C277 01 ...
Page 28: ...Index CP 5613 A3 CP 5614 A3 28 Operating Instructions 10 2012 C79000 G8976 C277 01 ...