3
Installation and Commissioning
B4 - 13
CP 443-5 Extended for PROFIBUS / Manual Part B4
Release 6/2005
C79000-G8976-C162-06
3
Installation and Commissioning
!
Caution
The CP 443-5 Extended must not be plugged in or removed when the power is
connected.
If you do remove or insert the CP while it is powered on, the CPU changes to
STOP; this does not cause damage to the CP. Afterwards, you must turn the
power for the central rack off and on again.
Procedure / Steps
Step
Explanation / Meaning
1. Insert the CP 443-5
Extended
The CP 443 - 5 Extended can be operated in the following racks:
S
Central rack CR2, CR3
S
Universal rack UR1 UR2 or UR2H
as the central
or expansion rack with rack no. 1 - 6 (only possible if there is no DP
operation).
The CP 443-5 Extended cannot be used in an ER1 or ER2 expansion rack.
Suitable slots in the rack:
With the exception of the slots reserved for the power supply and IM-R, the
CP 443-5 Extended can be inserted in all slots with a P and K bus interface
(in the central or in an expansion rack no. 1 - 6).
Notice
When you are using PROFIBUS-DP, the module must only be operated in the
central rack!
When using the universal rack as an extension rack, you require an IM with a
communication bus link!
Step
Explanation / Meaning
2. Attachment to
PROFIBUS
Note the information in the General part of this manual.