Siemens CLM Series Instructions & Installation Manual Download Page 8

Problem

Contacts 
Contacts Chatter 

Welding 

Coils 

Open 

Circuit 

Overheated 

Coil 

Failure to Drop-Out  

Cause 

Low Voltage 

Abnormal  Inrush Current 

Insufficient Contact  Pressure 

Foreign Matter  Preventing  Contacts 

from Closing 

Foreign Matter  Preventing  Proper 

Latch Motion 

Short Circuit 

Excessive Inrush Current 

Filing or Dressing 

Foreign  Matter on  Contact Surface 

Mechanical Damage 
Incorrect Coil 

Low Voltage 

Wrong  Coil or Wrong  Connection 

Mechanical  Obstruction 

Coil Open or Overheated 

Sticky Substance  on Pole Faces 

Release  Coil not Energized 

Contacts Welded 

Corrective Action 

Check supply voltage, especially during starting. Check coil voltage rating. 

Increase voltage or change coil rating as required.  

Check for grounds, shorts or excessive load current.  

Replace contacts and springs, check contacts for abnormal wear or damage. 

Check supply voltage to coil, especially for momentarydip during startup.  

Clean contacts with LPS CFC-Free Electro Contact Cleaner. 

Contacts used at low currennt and voltage should be cleaned with  Freon.  

Clear latch mechanism of foreign matter.

Check that latch mechanism moves properly.  

Remove fault and check to be sure fuse or breaker size is correct.  

Use next larger size contactor.  

DO NOT FILE SILVER CONTACTS.  Rough spots or discoloration will not 

harm contacts or impair their efficiency.  

Check for grounds, shorts or excessive currents. Use next larger size contactor.  

Replace contacts and springs, check contacts for abnormal wear or damage.  

Clean contacts with LPS CFC-Free Electro Contact Cleaner. 

Take steps to reduce entry of foreign matter into enclosure.  

Remove fault and check to be sure fuse or breaker size is correct.  

Clean and tighten.  

Replace with new coil. Handle and store new coils carefully. 

Check coil rating and replace with correct coil. 

Check coil marking and wiring.  

With power off, check for movement of armature, contacts and latch 

mechanism.  

Replace. 

Clean pole faces with LPS CFC-Free Electro Contact Cleaner.  

Check coil, coil circuit or length of leads from supply voltage to coil. 

Coil may be open or lead length is excessive.  
Replace unit.  

See welding under contacts.  

TROUBLESHOOTING 

These instructions do not purport to cover all details or variations in equipment nor to 

provide for every possible contingency to be met in connection with installation, 

operation, or maintenance. Should further information be desired, or should problems 

arise which are not covered sufficiently for the purchaser’s purposes, the matter should 

be referred to the local Siemens Sales Office.

8

Weak Contact Pressure 

Low Voltage Preventing Magnet 

from Sealing 

Short Contact Life 

or Overheating 

Interrupting Excessively High Currents 

Short Circuit 

or Ground Fault 

loose Connection in Power Circuit 

Magnetic and 

Mechanical Parts

Failure to Pick-up and Seal 

Worn or Rusted Parts Causing 

Binding 

Check system voltage and voltage dips during starting 

The contents of this instruction sheet shall not become part of or modify any prior or existing 

agreement, commitment or relationship. The sales contract contains the entire obligation of 

Siemens. The warranty contained in the contract between the parties is the sole warranty of 

Siemens. Any statements contained herein do not create new warranties or modify the existing 

warranty.

Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092

A5E49381767A

Summary of Contents for CLM Series

Page 1: ...r closes the latch lever hooks over the latch pin to mechanically latch the contactor closed The Coil Clearing Auxiliary Contact deenergizes the closing coil Opening When the Trip pushbutton is operated the trip solenoid coil is energized unhooking the latch lever from the latch pin which allows the contactor to open As the contactor opens the Coil Clearing Auxiliary Contact deen ergizes the trip ...

Page 2: ...Fig 1 400 Ampere CLM0H03 Contactor Exploded View 1 8 2 9 4 7 6 14 12 18 15 13 14 11 3 5 17 16 19 2 Siemens Industry Inc 5300 Triangle Parkway Norcross GA 30092 A5E49381767A ...

Page 3: ...olted in place The arc chute 2 provides the mechanical stop for the moving contact assembly while maintaining the proper open gap for the main contacts The arc chute also contains the De ion type arc quenchers Two front accessible bolts 1 hold the arc chute in place This arc chute requires no maintenance except for periodic inspection for grid damage or ceramic liner burn through by fault conditio...

Page 4: ...nt 1 Latch Adjustment refer to Figures 1 7 and Table 2 Manually close the contactor to the fully closed position Loosen latch bolts 10 Move latch 11 to obtain 0 003 to 0 007 inch clearance shown Retighten latch bolts to 90 100 lb in while maintain ing clearance 2 Trip Solenoid Adjustment refer to Figures 1 7 and Table 2 Manually close the contactor to the fully closed position Note that the latch ...

Page 5: ...he bolts per Table 2 Contact Overtravel and Replacement refer to Figures 1 9 10 and Tables 2 and 5 CAUTION The contactor must never be operated in power circuit unless the arc chute is securely bolted in place Remove all power from the contactor and the operating coils With new contacts the initial contact overtravel is 5 32 to 13 64 inches The overtravel is measured as shown in Figures 9 and 10 R...

Page 6: ...of Latch and Trip Solenoid Contactor Closed Fig 8 Adjustment of Coil Clearing Auxiliary Contact Contactor Open Fig 6 CLM0H03 Dimension Drawing 6 Siemens Industry Inc 5300 Triangle Parkway Norcross GA 30092 A5E49381767A ...

Page 7: ... are in back of each magnet part The moving armature has less spring force and restraint than the stiffer stationary magnet assembly In case these mag nets are ever disassembled particular care must be used to make sure that the flat leaf springs are centered on the laminated magnet assemblies and are not jammed between the magnets and the molded guide projections After reassembly be sure to check...

Page 8: ...matter into enclosure Remove fault and check to be sure fuse or breaker size is correct Clean and tighten Replace with new coil Handle and store new coils carefully Check coil rating and replace with correct coil Check coil marking and wiring With power off check for movement of armature contacts and latch mechanism Replace Clean pole faces with LPS CFC Free Electro Contact Cleaner Check coil coil...

Reviews: