15
Siemens Building Technologies
Cerberus Division
e3180a.doc
12.2000
5.3 Automatic
measurement
In the
Auto Test
operating mode all the measuring functions activated in the template
are automatically carried out consecutively. The LEDs light up as the corresponding
measurement is carried out.
The templates, measured data and result display are always determined by the device
(master) used to initiate measurement. Normally this is the device SLT-22. The SLT -11
device (slave) connected at the far end of the line is remote controlled by the master.
The first measurement always begins with the template for the highest quality cable.
5.3.1 Measurement
1.
Select operating mode
Auto Test
➜
LED Auto Test lights up
2.
Press
Start/Stop
key
➜
LED
Att, DC-R, User Def
lights up, as the measurement is carried out.
A
measuring sequence lasts approximately 30sec.
3.
Display at the end of measuring through Pass/Fail assessment"
➜
Display
PASS
specified threshold complied with
➜
Display
FAIL Near
specified threshold
NOT
complied with
➜
Display
FAIL Far
specified
threshold
NOT
complied with
Pass/Fail assessment