Operation (short)
FC120
Fire control panel (NL)
Document ID: A6V10393200_a_en_--
ALARM Procedure
with Alarm Verification Concept (AVC)
Action / Condition
Press
on the PMI
.
before allowed
(V1) runs out (Password required)
Read time of top line right side on the display
Read fire location on display.
Go to the fire location.
Decide:
MAJOR INCIDENT
or
minor incident
MAJOR INCIDENT
:
Press
<alarm delay off>
o
r actuate nearest
manual call point.
Look at the LED indicator
'On: Fire brigade called'
'Off: Call fire brigade!'
(
Remote transmission is switched off / not
available or defective)
Minor incident
:
Press
to reset the panel.
(Password required)
Press
twice.
Press
twice.
1.
2.
3.
4.
5.
A
R
6.
B
4.
Fire alarm 2:00
Zone 1 1/1
Meeting room 1
3.
Decide:
MAJOR INCIDENT or
5.
Go to the fire location.
B
7.
ALARM-Procedure
Switching off detector zones
Switching on detector zones
Procedure in case of Fault
Edition: 2013-07-24
Alarm Verification Concept (AVC) – suggested possible procedure – subject to local requirements
Consequence / Status
before allowed reaction time
Buzzer is turned off, alarm is acknowledged.
Countdown V2 for the investigation of the cause of alarm starts.
top line right side on the display
Remaining time is shown as countdown before Fire Brigade call.
Information on the cause of ALARM
minor incident
.
If required, initiate suitable emergency measures.
<alarm delay off>
manual call point.
The remote transmission for fire alarm is activated immediately.
Remote transmission is switched off / not
ALARM is transmitted to fire brigade.
Fire brigade must be called by phone!
–
No automatic transmission to fire brigade
–
Dial the following no.:
to reset the panel.
Fire detection system is in normal condition unless another event
occurs. It may be necessary to vent the room
possible. Elements that cannot be reset c
temporarily.
Stop
the evacuation.
Start
the evacuation.
1.
R
2:00
Zone 1 1/1
2.
MAJOR INCIDENT or
Minor incident
the fire location.
Siemens Switzerland Ltd
Industry Sector
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Page 1
Page 2
Page 3
Page 4
1 / 4
subject to local requirements
Buzzer is turned off, alarm is acknowledged.
2 for the investigation of the cause of alarm starts.
Remaining time is shown as countdown before Fire Brigade call.
Information on the cause of ALARM
If required, initiate suitable emergency measures.
The remote transmission for fire alarm is activated immediately.
ALARM is transmitted to fire brigade.
phone!
No automatic transmission to fire brigade
Fire detection system is in normal condition unless another event
occurs. It may be necessary to vent the room before resetting is
possible. Elements that cannot be reset can be switched off
6.
A
7.