On the detector itself there is no mechanical adjustments. All function changes are initiated
remotely by the control unit. The factory programs all detectors with a basic parameter set.
This ensures that each detector is fully functional when it is installed. The additional param-
eter sets can be programmed in the field with the service PC by downloading them from the
control unit.
9.2.1
DOT1151A-Ex
Parameter set
Risk exposure and influence
Risk exposure
APS083S
!
Low concentration of valuable property;
no direct danger to life;
No danger of smouldering fire!
Aerosols arise regularly and for a length of time in ”Manned”
mode. No simultaneous thermal influence. No or few aero-
sols in ”Unmanned” mode.
Discotheques/dance halls, places of
entertainment with artificial smoke or
fog.
Caution, use very restrictively!
APS005S
(foctory default)
Low to moderate concentration of valuable property;
no direct danger to life.
No ban on smoking.
Industry, workshop halls,
diesel vehicle traffic, park garage,
restaurants, kitchen, smoking rooms
APS082S
––> Only for application in the China region in compliance
with Chinese standards;
––> As for APS005S, but with modified thermal response.
as for APS005S
APS015S
––> As for APS005S, but specially for applications at sea
level as it has a slightly faster reaction than APS005S.
as for APS005S
APS006S
Moderate concentration of valuable property;
no direct danger to life.
No ban on smoking.
Offices, warehouses,
electric vehicle traffic,
congress centers.
APS085S
Medium to high concentration of valuable property;
Person self-rescue is possible.
No ban on smoking; little thermal influence.
Museums, warehouses, offices.
APS084S
!
Low concentration of valuable property;
no direct danger to life;
low risk of smouldering fire.
Aerosols arise briefly at times without simultaneous thermal
influence.
Special production areas with trans-
ient and nonrecurring aerosols.
Caution, use very restrictively!
APS009S
High concentration of valuable property;
Person self-rescue is possible.
No ban on smoking.
Storerooms, hotel rooms, home for
the elderly rooms, schools,
data processing and telecommuni-
cation systems in clean environe-
ment.
APS019S
––> As for APS009S, but specially for applications at sea
level as it has a slightly faster reaction than APS009S.
as for APS009S
APS007S
High concentration of valuable property;
Persons partly endangered.
Ban on smoking.
Clean warehouses, museums,
archives,
data processing and telecommuni-
cation systems in clean environe-
ment.
APS081S
Very high concentration of valuable property;
Persons endangered.
Ban on smoking; no thermal influences.
Clean rooms, patient rooms,
museums.
APS080SH
!
Extremely high concentration of valuable equipment;
persons endangered.
Total ban on smoking, no other aerosols;
no thermal influences
.
Patient rooms, intensive care unit,
clean rooms.
Caution, use restrictively!
The parameter sets listed here are arranged in order of sensitivity (APS080SH is the most
sensitive).
For planning and project planning see «Application guidelines», document e1225, manual
DS11, section 10