background image

Siemens Industry, Inc.
Building Technologies  Division

P/N 315-034200-9

4

WIRING

Remove all system power before installation, first battery, then AC. (To power up,

connect the AC first, then the battery.)

All device field wiring to the CDC-4 is connected to the terminal blocks of the CC-5
card cage slot in which it is installed.

To Connect the External Wiring:

1.

Loosen the screw of the
terminal by turning it counter-
clockwise.

2.

Insert the wire into the side of
the terminal block

3.

Tighten the screw of the
terminal block by turning it
clockwise.

C24V from PSC-12 to terminal
17 and -24V from PSC-12 to terminal 18
of the slot in the CC-5 where the CDC
will be installed using 12-18 AWG (Refer
to Fig.2).

Refer to Figure 3. All circuits are power
limited to NFPA 70 per NEC 760. Each
detector or group of detectors must use
a two-wire circuit of at least 18 AWG,
thermoplastic fixture wire, enclosed in
conduit. If permitted by local building
codes, 18 AWG limited energy, shielded
cable without conduit may also be used.

The CDC-4 may be connected to existing
device loops that have a 3.9K or 4.7K
end-of-line resistor (

1

/

4

W, 5%) or a 50uF,

50V end-of-line capacitor installed. Always use a 50uF, 50V end-of-line capacitor for
new installations and whenever practical in existing detector loops for all detector
models except the Siemens PBA-1191, which requires a 4.7K end-of-line resistor, as
shown in Figure 3.

Total circuit resistance must not exceed 70 ohms—40 ohms if accessories (relay/
audible bases) are used.

Each detector zone can be wired Class A or Class B individually.

 The screw terminals can accommodate one 12 -18 AWG or two 16-18 AWG.

All unused zones must be terminated with a 50uF capacitor (Terminals 1 and 4 for

Zone 1, Terminals 5 and 8 for Zone 2, Terminals 9 and 12 for Zone 3, and Terminals 13

and 16 for Zone 4).

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

LINE+

(OUT)

LINE+

(OUT)

LINE+

(OUT)

LINE+

(OUT)

LINE-

(OUT)

LINE-

(OUT)

LINE-

(OUT)

LINE-

(OUT)

LINE-

(RETURN)

LINE-

(RETURN)

LINE-

(RETURN)

LINE-

(RETURN)

LINE+

(RETURN)

LINE+

(RETURN)

LINE+

(RETURN)

LINE+

(RETURN)

24V+

24V–

ZONE 1

ZONE 3

TO 24VDC FROM PSC-12

ZONE 2

ZONE 4

ONE SLOT OF CC-5 FOR CDC-4

17

18

19

20

21

22

23

24

Figure 2

Wiring 24V Power Lines

Summary of Contents for CDC-4

Page 1: ... functions to operate Any circuit in an alarm or trouble condition is displayed on the PMI PMI 2 PMI 3 The CDC 4 is designed to function in a local degrade mode during failure of the FireFinder XLS main processor or during the loss of the system communication network While in the degrade mode the CDC 4 can report both alarm and trouble conditions and can activate local outputs on other modules wit...

Page 2: ...e reset switch and their functions are defined as follows POWER Green Normally ON When illuminated indi cates that power for the CDC 4 is applied to the card CARD FAIL Yellow Normally OFF When illuminated indi cates that the card microprocessor has failed HNET FAIL Yellow Normally OFF When illuminated indi cates that the HNET communication with the CDC 4 has terminated and the card goes into degra...

Page 3: ...LE Yellow Normally OFF When illuminated indicates that a trouble condition has been de tected in Zone 4 It will stay on continu ously until the condition is cleared ZONE 4 CLASS A OPEN Yellow Normally OFF When illuminated indi cates that there is a break in the Class A wiring in Zone 4 Three rotary dial switches at the bottom of the front panel are used to set the HNET network address of the CDC 4...

Page 4: ... without conduit may also be used The CDC 4 may be connected to existing device loops that have a 3 9K or 4 7K end of line resistor 1 4W 5 or a 50uF 50V end of line capacitor installed Always use a 50uF 50V end of line capacitor for new installations and whenever practical in existing detector loops for all detector models except the Siemens PBA 1191 which requires a 4 7K end of line resistor as s...

Page 5: ...or List for the maximum number of detectors per zone 5 Do not mix smoke detectors with the PBA 1191 6 Do not mix different manufacturer s smoke detectors on the same zone 7 Max resistance 70 ohms circuit 40 ohms circuit if accessories relay audible bases are used 8 Do not use shorting devices on circuits with accessories on them 9 Only one device accessory per circuit is guaranteed to activate on ...

Page 6: ...p the system and verify that the CDC 4 power LED turns ON INITIATING DEVICES Refer to the UL Compatible Two Wire Detector List for the number of detectors that may be used on a CDC 4 zone Refer to Figure 3 for initiating device wiring All circuits are power limited to NFPA 70 per NEC 760 Each detector or group of detectors must use a two wire circuit of at least 18 AWG thermoplastic fixture wire e...

Page 7: ... a B V 4 2 0 t n e r r u C V 4 2 l a n i m r e T w e r c S y r o s i v r e p u S x a m e n o z r e p A m 8 A m 0 1 1 y r o s i v r e p u S x a m e n o z r e p A m 8 A m 0 1 1 m r a l A x a m e n o z r e p A m 0 2 3 A m 0 1 1 m r a l A x a m e n o z r e p A m 0 8 2 A m 0 1 1 t n e r r u C e n a l P k c a B V 2 6 x a m A m 0 5 1 t n e r r u C y b d n a t S V 4 2 y r o s i v r e p u S x a m e n o z r...

Page 8: ...T 4 B D S T 4 B D F T 4 B D 0 3 0 3 Y s n e m e i S 6 I D 6 I D S T 4 B D F T 4 B D S T 4 B D F T 4 B D 0 3 0 3 Y s n e m e i S 5 3 1 P 3 T D 5 3 1 P 3 T D S 3 B D S 3 B D d e t i m i l n U Y s n e m e i S 1 1 T D 1 1 T D 1 1 B D T P D A w S 3 B D 1 1 B D S 3 B D 0 3 0 3 Y s n e m e i S 1 2 1 I H 1 2 1 I H E 1 1 B D 1 1 B D E 1 1 B D 1 1 B D 0 3 0 3 Y Y s n e m e i S 1 2 1 H O 1 2 1 H O E 1 1 B D ...

Page 9: ... 6 5 4 1 3 2 1 8 6 5 4 2 3 2 1 8 6 5 4 0 0 2 1 8 6 5 4 0 2 2 1 8 6 5 4 7 2 2 1 8 6 5 4 0 3 2 1 8 6 5 4 1 3 2 1 8 6 5 4 2 3 2 1 8 6 5 4 0 3 0 3 5 2 5 2 5 2 0 3 N o l l o p A 0 8 3 0 0 0 5 5 0 8 3 0 0 0 5 5 0 0 2 1 8 6 5 4 0 2 2 1 8 6 5 4 7 2 2 1 8 6 5 4 0 3 2 1 8 6 5 4 1 3 2 1 8 6 5 4 2 3 2 1 8 6 5 4 0 0 2 1 8 6 5 4 0 2 2 1 8 6 5 4 7 2 2 1 8 6 5 4 0 3 2 1 8 6 5 4 1 3 2 1 8 6 5 4 2 3 2 1 8 6 5 4 0 2...

Page 10: ...c e l E L S E T C 9 2 4 A 0 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T F A C 1 1 5 A 0 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T F A C 8 1 5 A 0 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T X B B 1 2 5 F F O 1 w S w A 0 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T X R C 1 2 5 F F O 1 w S w A 1 1 S A N A N 5 3 N l a n g i S o r t c e l E L S E T X B B 8 2 5 F F O 1 ...

Page 11: ...2 4 S N 0 2 2 6 S N 3 B H 5 1 5 1 Y Y i k i h c o H 4 2 J I S 3 D H 4 2 2 4 S N 4 2 2 6 S N 5 B H 5 1 5 1 Y Y i k i h c o H F 4 2 K L S H F 4 2 K L S 3 D H D 2 2 S H 2 2 M A B Y 3 B H 3 B H 0 2 0 2 Y Y i k i h c o H F 4 2 K L S H F 4 2 K L S 3 D H D 4 2 2 S H 4 2 2 M A B Y 5 B H 5 B H 0 2 0 2 Y Y i k i h c o H F 4 2 K L S H F 4 2 K L S 3 D H 4 2 2 B S H 3 5 B H 0 2 0 2 Y N i k i h c o H F 4 2 K L ...

Page 12: ...4 B 1 0 4 B B 6 0 4 B d n a A 5 2 Y r o s n e S m e t s y S K R B H D 1 5 4 1 A 0 0 4 H D A 5 2 N r o s n e S m e t s y S K R B 1 5 1 2 A d n a P L 0 1 1 B P L 6 1 1 B A 5 2 Y r o s n e S m e t s y S K R B T 0 0 3 2 A A N A N 5 2 N r o s n e S m e t s y S K R B 0 0 4 2 A A N A N 5 2 Y r o s n e S m e t s y S K R B H T 0 0 4 2 A A N A N 5 2 Y r o s n e S m e t s y S K R B 1 5 4 2 A B 1 0 4 B 1 0 4 ...

Page 13: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Page 14: ...Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada P N 315 034200 9 Document ID A6V10239127 ...

Reviews: