PROFIBUS MODULE (CB15/CB155)
English
Operating Instructions
16
6
7
8
Transmit number of array elements
Task not executable (with error number)
No exclusive use of PKW interface
Reply Identifiers (Inverter
_
Master)
Error
Number
Meaning
0
1
2
3
4
5
7
9
No reply
Parameter value cannot be changed
Lower or upper value limit exceeded
Error in sub-index
Not an array
Incorrect data type
Description element cannot be changed
Description data does not exist
Reply Error Codes (Inverter
_
Master)
Example:
Fixed setpoint 1: P41 = 29 (HEX)
Change parameter value.
Parameter Identifier (PKE)
1st word
Bit No.:
15
12
11
10
0
AK
SPM
PNU
0
0
1
0
0
0
0
0
0
0
1
0
1
0
0
1
Binary value
2
0
2
9
HEX value
Bit 12 .. 15: Value = 2 (= ‘2’ Hex); change parameter value (word)
Bit 0 .. 11:
Value = 41 (= ‘29’ Hex); parameter number without enabled spontaneous message bit
Figure 5:
Parameter Identifier Example
Parameter Index (IND) (2nd Word)
The index (also referred to as a subindex in the PROFIBUS profile) is an 8-bit value and is always transmitted on
PROFIBUS-DP in the most significant byte (bits 8 to 15) of the parameter index (IND); the least significant byte
(bits 0 to 7) of the parameter index (IND) has the value 0.
When a parameter has an index, the index is also transmitted. The number of the element is transmitted with a
description element. The meaning of the description elements is given in the PROFIBUS variable speed drives
profile (VDI/VDE 3689).
The index is not used for the inverter’s basic parameter set.