Chapter 4 - Parameters and Menu Structure
Parameters (M3)
99 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.13.2.4
SP 1 Source
Not Used
Test
Sequence
Keypad
SP1
1643
See Table
Setpoint Sources.
AIs and ProcessDataIn settings are
handled as percent and scaled
according to Setpoint Min and
Setpoint Max.
NOTE: Settings 9 through 16 use
two decimal places.
P3.13.2.5
SP 1 Minimum
%
-200
200
0
1644
Minimum value of Setpoint at
Analog Signal Minimum.
P3.13.2.6
SP 1 Maximum
%
-200
200
100
1645
Maximum value of Setpoint at
Analog Signal Maximum.
P3.13.2.7
SP 2 Source
Not Used
Test
Sequence
Not Used 1646
See
SP1 Source (P3.13.2.4).
P3.13.2.8
SP 2 Minimum
%
-200
200
0
1647
Minimum value of Setpoint at
Analog Signal Minimum.
P3.13.2.9
SP 2 Maximum
%
-200
200
100
1648
Maximum value of Setpoint at
Analog Signal Maximum.
Feedback (M3.13.3)
Table 66: PID Controller 2 Feedback.
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.13.3.1 Function
Source1
Mean
Source1 1650
Settings:
1 = Only Source 1 in use
2 = SQRT(Source1); (Flow =
ConstantxSQRT(Pressure))
3 = SQRT(Source1-Source2)
4 = SQRT(Source1) + SQRT(Source2)
5 = S Source2
6 = Source1 - Source2
7 = Min(Source1, Source2)
8 = Max(Source1, Source2)
9 = Mean(Source1, Source2)
P3.13.3.2 Gain
%
-1000
1000
100
1651
Used with selection 2 in Feedback
Function (P3.12.3.1)
P3.13.3.3 FB 1 Source
Not Used
ProcessDataIn8
AI1
1652
See Table
Feedback Sources.
AIs and ProcessDataIn settings are
handled as % and scaled according to
feedback min and max.
NOTE: Settings 7 through 14 use two
decimal places.
P3.13.3.4 FB 1 Minimum
%
-200
200
0
1653
Minimum value at Analog Signal
Minimum.
P3.13.3.5 FB 1 Maximum
%
-200
200
100
1654
Maximum value at Analog Signal
Maximum.
P3.13.3.6 FB 2 Source
Not Used
ProcessDataIn8
AI2
1655
See
FB 1 Source (P3.12.3.3).
P3.13.3.7 FB 2 Minimum
%
-200
200
0
1656
Minimum value at Analog Signal
Minimum.
P3.13.3.8 FB 2 Maximum
%
-200
200
100
1657
Maximum value at Analog Signal
Maximum.