Commissioning 

1.  Open the door by unlocking the 

locks

2.  Before switching ON, re-check 

external connections.

3.  Set Overload relay to 0.58 times the 

rated motor current.

4.  Set the dial of the Timer to an 

approx. value of starting time of 

Motor (preferably more than 6 secs)

A.  Star-delta Timer setting

1.  First Start the motor by pressing 

Green push button, marked "I"

2.  Measure time taken for it to reach 

nearly rated speed or steady state 

current (indicated when motor hum 
reaches a steady pitch)

3.  Stop the Motor, set Timer to this 

measured value, by rotating the 
Timer dial.

B.  Relay Settings

1.  For Closer protection set the 

Overload Relay to the phase current 
as measured by an ammeter.

2.  In absence of Ammeter, use 

procedure as given below:

a)  Start the motor and let it run 

for half an hour. Then gradually 
reduce relay setting till it trips. 
Set Relay at a  slightly higher 
value of this setting.

b)  Allow reset time of approx. 4 

min. Press the blue knob on the 
relay completely to reset the 
relay.

c)  Re-start motor after some 

time. If the relay does not trip, 
consider it to be properly set. If it 
trips follow step b with setting at 
little higher value and recheck.

d)  Overload relay characteristics 

given below can be used to 

estimate the average tripping 
time at different multiples of set 
current.

Caution: 

1.  Switch OFF the Starter, and 

disconnect the main supply by 
switching OFF the main switch 
before doing any maintenance.

2.  Under No Circumstances should 

the Relay be set higher than phase 
current i.e.. 0.58 times the rated 
current on the motor nameplate.

3.  If the Relay trip even when set 

at the rated Motor current, the 
suitability of the starter or relay for 
the particular application should be 
checked with the nearest Siemens 

office.

4.  Refer Table 1 for the Motor current  

corresponding to the Motor rating.

     

Figure 2: Timer Adjustment

     

Figure 3: Relay setting Adjustment

     

Figure 4: Maximum permissible angle from 
vertical plane

Table 1: Technical Details 

Motor Rating 

at 415V, 3ph, 

50Hz

Motor Current

"Type 

(ASD)"

Contactor

Contactor

Birelay 

(Inbuilt)

Recommend-

ed Max. 

Back-up HRC 

Fuse rating 

SIEMENS 

make type 

3NA

Recommended Cu 

Cable with lugs in 

sq. mm

Line 

current

Phase 

current

MLFB

Delta/Main

Star

Incoming Outgoing

HP 

kW

I

L

(A)

I

ph

 (A)

3TF

3TF

Relay 

Range

Type

From 

Supply

To Motor

100

75

131

75.6

3TE05 94-2AR0

3TF49

3TF47

70-95A

3UA5800-8YZ1

160

50

25

125

90

156

90

3TE05 95-2AR0

3TF50

3TF47

70-95A

3UA5830-5B

160

70

35

150

110

189

109

3TE05 96-2AR0

3TF50

3TF50

95-120A

3UA5830-5D

200

95

35

180

132

227

132

3TE05 97-2AR0

3TF51

3TF50

115-180A

3UA6230-5B

250

120

50

* For Type-2 co-ordination chart, refer latest Price list of " LV switchgear - Motor control products"

2

Dial

Summary of Contents for Automatic Star-Delta 3TE05 2AR0 Series

Page 1: ...upon location of incoming and outgoing cables remove corresponding rubber Grommets Ensure dust proofing by using proper cable glands 5 Select Correct Size of Cables as specified in selection Table 1 Remove required length of insulation and using the hardware specified refer table 2 at the connection terminals fix the incoming and outgoing cables Tighten the screws firmly 6 Check that line and moto...

Page 2: ...erage tripping time at different multiples of set current Caution 1 Switch OFF the Starter and disconnect the main supply by switching OFF the main switch before doing any maintenance 2 Under No Circumstances should the Relay be set higher than phase current i e 0 58 times the rated current on the motor nameplate 3 If the Relay trip even when set at the rated Motor current the suitability of the s...

Page 3: ... it will be automatically reset in maximum 4 minutes The Motor can be restarted only after the relay is reset H Hand Reset A Auto Reset Blue Reset Knob Figure 6 Relay Front View Q1 Line Contactor Q2 Star Contactor Q3 Delta Contactor S1 ON Push Button I S0 OFF Push Button O S4 Reset Button of relay K1 Bimetal Relay Q4 Star Delta Timer Maintenance 1 Keep the interior dust free 2 Check the tightening...

Page 4: ...ns Siemens Products are environment friendly which predominantly consist of recyclable materials For disposal we recommend disassembling and separation into following materials METALS Segregate into Ferrous Non Ferrous types for recycling through authorised dealer Disposal Dimensional Drawings all dimensions in mm 3TE05 2AR0 Table 2 Hardware Information kW Incoming Terminals Outgoing Terminals Tig...

Reviews: