7SG11 Argus 8 Relay Settings
©2010 Siemens Protection Devices Limited
Chapter 3 Page 4 of 10
SETTING RANGE
DEFAULT
Clock Sync. From Status
sets the period of synchronisation of the clock to the
nearest second or minute. The synchronisation
occurs on energisation of the Clock Sync. status
input
Seconds or Minutes
Minutes
Default Screen Timer
sets the time delay after which, if no key presses
have been detected, the relay will begin to poll
through any screens which have been selected as
default instrument screens
10sec, 60sec, 5min, 1hour
5 min
Change Password
allows a 4 character alphanumeric code to be
entered as the password. Note that the display
shows a password dependant encrypted code on
the second line of the display
4 alphanumeric characters
NONE
2 Voltage Menu
SETTING RANGE
DEFAULT
Gn V Element 1 Operation
sets the mode of operation of Voltage Element 1,
whether under or over-voltage
OFF, O/V, U/V
OFF
Gn V Element 1 Setting
sets the pickup level of Voltage Element 1
5V – 200V step 0.5V
80V
Gn V Element 1 Delay
sets the DTL timer value for Voltage Element 1
0.00 – 20.00 step 0.01 sec
20.0 – 100.0 step 0.5 sec
100 – 600 step 1.0 sec
0.00 sec
Gn V Element 1 Hysteresis
sets the amount of hysteresis required i.e. the
PU/DO ratio
1% – 90% step 1%
2%
Gn V Element 1 O/P Phases
sets the number of phases required to operate
before an output can be given
Any 1, All
Any 1
Gn V Element 2 Operation
As per Element 1
OFF
Gn V Element 2 Setting
As per Element 1
80V
Gn V Element 2 Delay
As per Element 1
0.00 sec
Gn V Element 2 Hysteresis
As per Element 1
2%
Gn V Element 2 O/P Phases
As per Element 1
Any 1
Gn V Element 3 Operation
As per Element 1
OFF
Gn V Element 3 Setting
As per Element 1
80V
Gn V Element 3 Delay
As per Element 1
0.00 sec
Gn V Element 3 Hysteresis
As per Element 1
2%
Gn V Element 3 O/P Phases
As per Element 1
Any 1
Gn V Element 4 Operation
As per Element 1
OFF
Gn V Element 4 Setting
As per Element 1
80V
Gn V Element 4 Delay
As per Element 1
0.00 sec
Gn V Element 4 Hysteresis
As per Element 1
2%
Gn V Element 4 O/P Phases
As per Element 1
Any 1