background image

P/N 315-049708-5

Siemens Industry, Inc.
Building Technologies  Division

8

LOOP

WIRES.

SEE

COMP

A

TIBLE

CONTROL

EQUIPMENT

T

ABLE.

NO

COM

NC

LOOP

WIRES.

SEE

COMP

A

T

IBLE

CONTROL

EQUIPMENT

T

ABLE.

T

O

NEXT

DETECT

OR

OR

EOL

DEVICE

(1A)

T

O

REMOTE

DEVICE

(6)

CNTL

+

-

(5)

-+

+

-

ALARM

CONT

ACTS

125

V

AC,

24

VDC,

2.5A

SEE

NOTE

2

DEVICE

REMOTE

DEVICE LOOP

-

DEVICE LOOP

+

LOOP/REM

-

DEVICE

CONTROL

NOT USED

LOOP/REM

+

MODEL

AD2-P

T

O

NEXT

DETECT

OR

OR

EOL

DEVICE

+

-

T

O

SECOND

REMOTE

DEVICE

(SEE

MUL

TIPLE

REMOTE

DEVICES)

REM+

-

+

REM-

CONTL

REMOTE

ALARM

RELA

Y

COM

NC

NO

+

-

CNTL

-

+

+

DEVICE

LOOP

MODEL

AD2-PR

NOTE:

EOL

DEVICE

MUST

BE

COMP

A

TIBLE

WITH

SYSTEM

INITIA

TING

CIRCUIT

.

OBSER

VE

PROPER

POLARITY

WHERE

APPLICABLE.

(6)

(5)

(1A)

TB1

TB1

PE-1

1

PE-1

1C

PE-1

1

PE-1

1C

N

O

TES:

1.

Up to 30 air duct housings can be

installed on one initiating cir

cuit,

ex

cept as noted in Note 2.

2.

When an 

AD2-PR is used to contr

ol a

fir

e saf

et

y function,

 the 

AD2-PR must

be the ONL

Y de

vice on the initiating

cir

cuit.

3.

Do not use looped wir

e under

 base

terminal.

4.

Br

eak wire r

un to pr

ovide supervision

of connection.

5.

The gr

een gr

ounding scr

ew

 in the

wiring compar

tment of the air

 duct

housing is not used.

Figur

e 5

Typical Connections f

or

 the 

AD2-P / 

AD2-PR Using PE-1

1 / PE-1

1C Detector

s

If

remote

devices

are

supported

by

the

initiating

circuit,

each

detector/base

may

have

up

to

2

remote

devices

with

the

following

configurations

and

restrictions

only:

MUL

TIPLE

REMOTE

DEVICES

Remote Device

1

AD2-P

AD2-P

Remote Device

2

RLC-1

1,

RL

W

-1

1

RSAC-1

1,

RSA

W

-1

1

Restrictions

See

Note

2

See

Note

2

SEE

REMOTE

DEVICE

INSTRUCTIONS

FOR

WIRING

DET

AILS:

DEVICE

RLC-1

1,

RL

W

-1

1

RSAC-1

1,

RSA

W

-1

1

INST

ALLA

TION

INSTRUCTIONS

P/N

315-094925

P/N

315-094926

If the r

ela

y cont

acts are

being used to contr

ol 1

20

VA

C operated eq

uipment,

ensur

e that the conduit is

pr

operly at

ta

ched to the

internal metal gr

ound str

ap,

using the pr

oper

 conduit

loc

king nuts.

  

Failure t

o

p

ro

vide pr

oper

 grounding

m

ay r

esult in f

atal

electrical shoc

k and

violation of national and

local codes.

Summary of Contents for AD2-P

Page 1: ...ge ts on the page ts on the page ts on the page ts on the page 1 1 1 1 14 of this manual 4 of this manual 4 of this manual 4 of this manual 4 of this manual TECHNICAL DATA AIR DUCT CONDITIONS Temperature Range 32O F 0O C 100O F 38O C per UL 268 268A Altitude Range AD2 P AD2 PR and AD2 XHR No altitude limitations Relative Humidity Range 10 85 non condensing non freezing Air DuctVelocity Range 100 4...

Page 2: ...ems and NFPA 92A Recommended Practice for Smoke Control Systems OPERATION When the Models AD2 P AD2 PR and AD2 XHR are operat ing a sample of air is drawn from the duct and passed through the sampling chamber by means of the input sampling tube The air sample passes through the smoke detector mounted in the duct housing and is exhausted back into the duct through the outlet tube This detector is e...

Page 3: ...RETURN AIR BLOWER AIR DUCT HOUSING DAMPER DAMPER BLOWER FILTER PLENUM FRESH AIR INTAKE DAMPER D D Figure 1 Typical Mounting of Duct Housing OUTLET TUBE INPUT SAMPLING TUBE CENTER LINE OF DUCT C L Based on the results of these checks the LED indicator flashes as follows s d n o c e S l a v r e t n I h s a l F r o l o C h s a l F n o i t i d n o C 1 1 E P C 1 1 E P C 1 1 P F 1 1 P F 1 1 O P F H 1 1 ...

Page 4: ...c tion i e deflector plates elbows dampers etc In all situations confirmation of velocity and pressure differen tial within specifications is required The pressure differential between the input sampling high pressure tube and outlet low pressure tube for the AD2 Series smoke duct detector should be greater than 0 01 inches of water and less than 1 2 inches of water 3 Identify a code compliant loc...

Page 5: ... Clean all holes Sampling Tube Installation The AD2 Series duct smoke detectors use a specially notched sampling tube which may be ordered separately in one of four standard lengths ST 10 For duct widths of 6 to 1 0 ST 25 For duct widths of 1 0 to 3 0 ST 50 For duct widths of 3 0 to 5 0 requires support ST 100 For duct widths of 5 0 to 10 0 requires support This model is supplied as two 5 ft secti...

Page 6: ...the remaining position Once the tube is installed rotate the retainer back into place and tighten screw Mounting After securing the input and outlet tubes to the duct smoke unit or initially placing the tubes through the 1 holes drilled or punched in the HVAC duct to accept the input and outlet tubes and then attaching them to the duct unit hold the duct unit assembly in position and use 2 12 X 3 ...

Page 7: ...CKOUT Wiring The AD2 P AD2 PR and AD2 XHR should be connected as shown in Figures 5 6 and 7 Note any limitations on the number of detectors and restrictions on the use of remote devices permitted for each circuit The AD2 P is used with the PE 11 PE 11C and FP 11 FP 11C It is also used with the HFP 11 HFPO 11 detector in the FireFinder XLS FS 250 FC2005 FC2025 FC2050 FC901 FC922 or FC924 System The...

Page 8: ... be the ONLY device on the initiating circuit 3 Do not use looped wire under base terminal 4 Break wire run to provide supervision of connection 5 The green grounding screw in the wiring compartment of the air duct housing is not used Figure 5 Typical Connections for the AD2 P AD2 PR Using PE 11 PE 11C Detectors If remote devices are supported by the initiating circuit each detector base may have ...

Page 9: ...VICE NC COM NO ALARM RELAY COM NC COM NC NO TO NEXT ADDRESSABLE DEVICE TB1 TB1 TB1 MODEL AD2 P MODEL AD2 XHR MODEL AD2 XHR FP 11 FP 11C LOOP WIRES SEE COMPATIBLE CONTROL EQUIPMENT TABLE FP 11 FP 11C FP 11 FP 11C ALARM CONTACTS 125 VAC 24 VDC 2 5A SEE NOTE 1 ALARM CONTACTS 125 VAC 24 VDC 2 5A SEE NOTE 1 NO LOOP DEVICE ALARM RELAY COM NC NOT USED If the relay contacts are being used to control 120 V...

Page 10: ...or 5 TB3 5 or 6 TB1 1A TB1 TB1 TB1 MODEL AD2 P MODEL AD2 XHR MODEL AD2 XHR HFP 11 SFP 11 HFPO 11 SFPO 11 OPTIONAL REMOTE ALARM INDICATOR MODEL RL HC OR RL HW SEE NOTE 2 LOOP WIRES SEE COMPATIBLE CONTROL EQUIPMENT TABLE HFP 11 SFP 11 HFPO 11 SFPO 11 TO NEXT ADDRESSABLE DEVICE ALARM CONTACTS 125 VAC 24 VDC 2 5A SEE NOTE 1 ALARM CONTACTS 125 VAC 24 VDC 2 5A SEE NOTE 1 NO DEVICE LOOP OTHER LINE LINE 1...

Page 11: ...off the cover and set it aside Align detector with base and insert detector Rotate detector clockwise while gently pressing on it until the detector drops fully into base Then rotate the detector clockwise until it stops and snaps in place Replace cover and tighten the four screws To Remove Rotate the detector counterclockwise until stop is reached Pull detector out of base TESTING Only qualified ...

Page 12: ...2 second to release gas into the chamber DO NO DO NO DO NO DO NO DO NOT SPRA T SPRA T SPRA T SPRA T SPRAY GA Y GA Y GA Y GA Y GAS FOR MORE S FOR MORE S FOR MORE S FOR MORE S FOR MORETHAN SECOND THAN SECOND THAN SECOND THAN SECOND THAN SECOND O O O O OVER VER VER VER VER USE OF USE OF USE OF USE OF USE OF TES TES TES TES TEST GA T GA T GA T GA T GAS MA S MA S MA S MA S MAY RESUL Y RESUL Y RESUL Y R...

Page 13: ...echnician hnician hnician hnician hnician F F F F For or or or or service service service service service cont cont cont cont contact y act y act y act y act your our our our our nearest authoriz nearest authoriz nearest authoriz nearest authoriz nearest authorized Siemens Industry ed Siemens Industry ed Siemens Industry ed Siemens Industry ed Siemens Industry Inc Inc Inc Inc Inc S S S S Service R...

Page 14: ...9 C F 5 0 0 2 C F 4 2 9 C F 2 2 9 C F 0 5 0 2 C F 6 0 5 8 4 3 0 5 1 3 N P X E L X S 8 7 9 9 5 9 0 5 1 3 N P X E L X S X 4 E Z S 8 8 1 0 6 9 0 5 1 3 N P X E L X S X A 8 E Z S 8 2 2 0 6 9 0 5 1 3 N P C 0 5 2 S F M Z S 4 C 0 5 8 4 3 0 5 1 3 N P 3 M E T S Y S 5 3 U Z 8 1 2 2 2 3 8 0 5 1 3 N P R O T C E T E D 1 1 O P F H R O 1 1 P F H G N I S U R H X 2 D A D N A P 2 D A t n e m p i u q E e l u d o M r ...

Page 15: ... loading along with loop wire electrical specifications are provided in the applicable control unit instructions given in the above Compatible Control Equipment tables e g a t l o V C D V 7 2 6 1 e l p p i R k a e p o t k a e p V 3 t n e r r u C y r o s i v r e p u S x a m A u 0 1 1 e m i T p u t r a t S x a m s d n o c e s 0 5 C 1 1 1 1 E P r o t c e t e D r o t c e t e D C 1 1 1 1 E P e c i v e ...

Page 16: ...Siemens Industry Inc Building Technologies Division Florham Park NJ P N 315 049708 6 Siemens Canada Limited Building Technologies Division 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Reviews: