UM91-HF 

OPERATION 

Prior to turning on supply air, back off the adjusting screw until there is no compression of the range spring; refer to 
dimension and assembly drawings as needed.  After turning the supply pressure on, turn the adjusting screw clockwise to 
increase outlet pressure.

 

 

 

MAINTENANCE 

1) 

To remove condensate, slowly open the drain valve and bleed accumulated liquid.

 

 

2) 

To clean the filter element:

 

 

a. 

Shut off supply air.

 

WARNING

 

 

 

Components can be ejected with great force if the instrument 
is disassembled while pressure is applied.  To avoid the risk 
of death or serious injury, always turn off and vent supply 
pressure and any downstream pressure source when 
disassembling the instrument. 

 

b. 

Drain condensate.

 

c. 

Remove four corner bolts from the bottom of the unit. Refer to the Assembly Drawing as needed.

 

d. 

Remove drip-well housing and filter.

 

e. 

Clean parts and reassemble in reverse order.

 

 

Assembly Drawing 

 

3

 

Summary of Contents for 91-HF

Page 1: ...sumption Less than 5 SCFM 0 17 m3 hr Effect of Supply Pressure Variation Less than 0 2 psig 1 4 kPa for 25 psi 170 kPa change Ambient Temp Limits 0 to 160 F 18 to 71 C Weight 1 6 lb 725 g MATERIALS OF CONSTRUCTION Body Diecast Aluminum Alloy Irridite and Baked Epoxy Finish Filter 3 Micron Phenolic Impregnated Cellulose Diaphragm Nitrile Elastomer and Nylon Fabric Valve Seat Plug Nitrile Elastomer ...

Page 2: ... an appropriate certificate Non approved instruments are suitable for use with instrument air only Optional features and modifications such as tapped exhaust do not imply suitability for use with hazardous gases except as listed on an approval certificate CAUTION Synthetic compressor lubricants in the instrument air may cause deterioration of some components resulting in instrument failure See mat...

Page 3: ...accumulated liquid 2 To clean the filter element a Shut off supply air WARNING Components can be ejected with great force if the instrument is disassembled while pressure is applied To avoid the risk of death or serious injury always turn off and vent supply pressure and any downstream pressure source when disassembling the instrument b Drain condensate c Remove four corner bolts from the bottom o...

Page 4: ...to the Siemens Internet site and then click Process Instrumentation In the column to the right click Support Manuals In the column to the left select the product line e g Pressure or Temperature or Controllers to open navigation and search panes Note Navigation may change as the site evolves Warranty The sales contract contains the entire obligation of Siemens The warranty contained in the contrac...

Reviews: