1. Insert the absorber collar on both sides between the pressure relief duct and the front lateral
parts, and fasten with 4 bolts M6 each.
2. Mount offset plates if necessary [
Page 67, "Mounting the offset plates"]
Fig. 60:
Mounted absorber collar (panel
width 2 x 310 mm)
1
Left-hand absorber collar
2
Right-hand absorber collar
7.13.5.1 Mounting the offset plates
Do not mount the offset plates:
▪ If a low-voltage compartment is mounted.
▪ If voltage transformers are mounted at the busbar.
1
Front lateral part
2
Position of low-voltage compartment
3
Position of voltage transformer
4
Absorber collar
5
Installation dimension of offset plates
6
Offset plate
1. Measure the installation dimension
5
.
2.
If offset plates with an installation dimension between 120 mm and 190 mm are
required:
Shorten both offset plates at the notches with a side cutter.
2x
Fig. 61:
Shortening the offset plates
3. Fasten the offset plates between the absorber collar
4
and the lateral part
1
using 4 self-
tapping bolts M6.