C53000-B1100-C602-1
7XV5810 0xA00
Operating Instructions
Seite 9 von 20
1.15 Connection
The connection of the supply voltage is to be carried out according to
VDE0100 and VDE0160. The auxiliary supply of the device is to be provided
with an external disconnector (switch) for the safety isolation of the power
supply and with a safety device (fuse), 2 AT or 4 AT.
Warning
If you use litz wire, please use wire termination.
The external disconnector is to be labelled accordingly. A safety cutout can
possibly act in both functions.
Recommended stripping length: 5 mm.
The output voltage of the power supply conducted to the consumer must be
done with cables that are isolated twice or are separated from the network
cables.
1.16 Commissioning
Check whether the operation data comply with the values on the rating plate.
Do not make any changes at the device.
Clip the wide-range power supply on the top–hat rail with the help of clip-on
mounting.
Connect the auxiliary power to the terminals V
aux
(see chapter 2.5 und 0).
The device is ready for use after switching on the auxiliary power.
The green LED `RUN´ lights up.