background image

 

 
 

 

1.1 Qualified 

Personnel 

 
Tampering with the device/system or noncompliance with the safety 
notices given in this manual may cause severe bodily injury or property 
damage. Therefore any interventions on the device/system may only be 
performed by adequately qualified personnel. 
 
Qualified personnel as per the safety notices given in these instructions 
or on the product itself is: 
 
• personnel involved in planning and configuration activities and familiar 
with the safety concepts used in automation engineering; 
 
• operating personnel trained for working with automation systems and 
familiar with the content of this manual as far as it deals with operational 
aspects; 
 
• commissioning and service personnel having adequate training and 
qualification to repair this type of automation equipment and/or having 
authorization to commission, release, ground and tag devices, systems 
and electrical circuits. 
 

12.10.2006 

RS485-FO Converter 2-channel 

Page 5 of 28

 

Summary of Contents for 7XV5651-0 A00 Series

Page 1: ...RS485 FO Converter 2 channel 7XV5651 0xA00 for asynchron protocols up to 115 kBaud Operating Instructions Oct 2006 ...

Page 2: ......

Page 3: ...chanical Stress Tests 16 3 8 Dimension Drawings 17 3 9 Ordering Data 17 4 DESCRIPTION OF THE FUNCTIONAL UNIT 18 4 1 Terminal Assignment 18 4 2 Screw type terminals X2 X7 X5 19 4 3 RS485 Connector X6 19 4 4 FO Connections 20 4 5 Switch positions 20 4 6 Assignment Switch 1 21 4 7 Assignment Switch 2 21 5 INSTALLATION AND COMMISSIONING 22 5 1 Reference to Installation 22 5 2 Connection 22 5 2 1 Power...

Page 4: ...ructions and warnings given in this document in a general manner This manual is an integral part of the scope of delivery However it cannot take into account every detail on all types of the described product and also every possible case regarding installation operation or maintenance If further information is desired or in case special problems should arise which are not treated adequately in thi...

Page 5: ...self is personnel involved in planning and configuration activities and familiar with the safety concepts used in automation engineering operating personnel trained for working with automation systems and familiar with the content of this manual as far as it deals with operational aspects commissioning and service personnel having adequate training and qualification to repair this type of automati...

Page 6: ...th severe bodiliy injury or considerable property damage Attention Disregard of the corresponding precautionary measures may lead to slight bodiliy injury or minor property damage Note Shall draw your attention to special information on the product product handling or the corresponding section of the documentation Qualified personnel Commissioning and operation of the equipment is to be performed ...

Page 7: ... or compounds recommended or accepted by Siemens Faultless and safe operation of the product require proper transport storage mounting and installation as well as careful operation and maintenance 1 4 Explanation of the symbols at the device Danger Warning of a danger Please read the documentation To be operated only by qualified personnel Double insulation 12 10 2006 RS485 FO Converter 2 channel ...

Page 8: ...luded in the next edition You are invited to send us your suggestions for improvement 1 6 Copyright Copyright Siemens AG 2000 All rights reserved Transmission or reproduction of this document as well as the use and forwarding of its contents is not permitted without express written authority Offenders will be liable for damages All rights including rights created by patent grant or registration of...

Page 9: ...ion the line can be terminated using a resistor terminator The auxiliary power supply is fed in via 2 terminals Because of its extremely wide auxiliary voltage range DC 24 250 V and AC 60 250 V the converter can be connected without switchover to all common types of station batteries and AC mains voltage supplies The front cover has LEDs for indication of the operating voltage status green LED and...

Page 10: ...ive Light OFF in idle state incoming light signals are treated as active 1 high For use in systems operating with a negative logic the converter can be switched over to negative logic by means of a switch that is accessible from outside Inversion of the logic applies to both the optical input and the optical output of this interface On delivery the converter is set to positive logic Light OFF in i...

Page 11: ...age 24 V 250 V DC 20 24 V 230 V AC 20 45 65 Hz 1 25 A slow blow not changeable III With UH UHN typical value 3 W 2 5 W 3 5 VA Alarm relay 1 Relay Connector Test voltage Switching voltage nominal value Switching capability Switching current Fault indicator MSR Relay 1 NC open contact potential free 2 pol Phönix terminal 3 7 kVeff 250 V DC 20 W VA 1 A permanent LED green 5 V o k RS485 interface Conn...

Page 12: ...Transmitting data ch 2 820 nm 19dBm with 50 125µm multimode fibre 15dBm with 62 5 125µm multimode fibre 6 2dBm with 200µm HCS fibre 30dBm 10dB 3 dB system budget safety margin 3 0 km with 62 5 125µm multimode fibre 1 5 km in combination with SIPROTEC systems with 62 5 125µm multimode fibre 3 5 m with 980 1000 plastic fibre 9600 115200 Baud 3 2 Safety Tests Safety tests according DIN EN 61010 Part1...

Page 13: ... capacitors 3 7 kV AC 50Hz 1s without bypass capacitors 5 kV peak 1 2 50 µs 0 5 J 3 pos and 3 neg surges in intervals of 5 s all circuits class III not on open contacts 3 4 Interference Emission Interference Emission Standard EN 50081 1 Conducted interference only power supply voltage IEC CISPR 22 EN55022 VDE 0878 Teil 22 Radio interference field strength IEC CISPR 22 EN55022 VDE 0878 Teil 22 150 ...

Page 14: ...th HF field pulse modulated IEC 61000 4 3 ENV 50140 ENV50204 class III Fast transient disturbance burst IEC 61000 4 4 class IV IEC 60255 22 4 class IV EN 61000 4 4 class IV 1 MHz 400 surges per s dur 2 s 2 5 kV longit voltage 1 0 kV transverse voltage 4 kV contact discharge 8 kV air discharge both polarities 150 pF Ri 330 Ohm 10 V m 27 MHz to 500 MHz 10 V m 80 MHz to 1000 MHz 80 AM 1kHz 10 V m 900...

Page 15: ...z 80 AM 1 kHz 30 A m permanent 300 A m during 3 s 50 Hz 3 6 Climatic Stress tests Ambient Temperatures EN 60068 2 1 and 2 2 Recommended operating temperature Limiting temporary transient operating Limiting temperatutre during storage packing from the factory Limiting temperature during transport packing from factory Permissible humidity 5 C to 55 C 23 F to 131 F 20 C to 70 C 4 F to 158 F 25 C to 5...

Page 16: ... Frequency sweep rate 10 oktave min 20 cycles in 3 orthogonal axes semi sinusoidal Acceleration 5 g duration 11 ms 3 shocks in each direction of 3 orthogonal axes sinusoidal 1 Hz to 8 Hz 3 5mm amplitude horizontal axis 1 Hz to 8 Hz 1 5mm amplitude vertical axis 8 Hz to 35 Hz 1g acceleration horizontal axis 8 Hz to 35 Hz 0 5g acceleration vertical axis Frequency sweep rate 1 octave min 1 cycle in 3...

Page 17: ...DC 60 230V AC RUN T1 R1 UH UH L1 L 1 2 M1 A B RCV1 T2 R2 90 75 105 90 90 Fig 1 Dimension Drawings 3 9 Ordering Data Name Order No RS485 FO Converter 7 X V 5 6 5 1 0 A 0 0 with 2 FO Interfaces and 1 RS485 Interface Optical In Output BFOC ST connector B 12 10 2006 RS485 FO Converter 2 channel Page 17 of 28 ...

Page 18: ...o the 9 pin SubD socket The two fiber optic channels are connected by BOFC ST terminals The unit is free of silicone and halogen as well as flame retardant 4 1 Terminal Assignment N L RS 485 RS485 LWL Converter 7XV5651 0AA00 SERIES A4 K7 655430 C E 5 5 24 250V DC 60 230V AC RUN T1 R1 UH UH L1 L 1 2 M1 A B RCV1 X6 X2 X7 X5 R2 T2 Tx FO transmitter Rx FO receiver X2 Power supply X5 RS485 terminals X6...

Page 19: ...85 connector pin A A X5 Pin 2 RS485 connector pin B B Tab 1 Screw type terminals X2 X7 X5 4 3 RS485 Connector X6 Pin Bedeutung Abkürzung 1 not connected 2 not connected 3 RS485 Connector Pin A A 4 not connected 5 Signal ground GND 6 Power supply 5V DC VCC 7 not connected 8 RS485 Connector Pin B B 9 not connected Tab 2 RS485 Connector Sub D 9 pol female X6 12 10 2006 RS485 FO Converter 2 channel Pa...

Page 20: ...se tools The ST plugs are to be shifted with the lateral nose into the groove of the device connection and locked afterwards During the installation of the FO cables the bending radius specified for the cable is to be kept 4 5 Switch positions The DIP switches can be actuated from outside OFF X6 X2 X7 S1 ON X5 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 OFF ON S2 Down view Fig 3 Switch positions S1 S2 Page 20...

Page 21: ... changed 7 7 off on Light ON in idle state Channel 2 Light OFF in idle state Channel 2 8 8 off on Light ON in idle state Channel 1 Light OFF in idle state Channel 1 Tab 2 Assignment S1 4 7 Assignment Switch 2 Switch S2 Position Meaning 1 2 3 4 5 6 7 8 off off off off off on on off May not be changed Tab 3 Assignment S2 12 10 2006 RS485 FO Converter 2 channel Page 21 of 28 ...

Page 22: ...d only for operation within enclosed housings or cabinets and places of installation are to be accessible only for qualified personnel The device is clipped on a 35 mm top hat rail according to EN50022 The installation location should be free of vibrations The admissible temperature operation or functional temperature is to be observed see technical data Disregard of the temperature range required...

Page 23: ...are screwed on terminal X7 at he bottom side of the device The assignment of the terminals is printed at the front side or can be read in this manual Connection to screw terminals Terminal cross section max 2 5 mm2 Stripping length 3 bis 5 mm Cable cross section 0 14 bis 1 5 mm2 Single core cable or litz wire 5 2 3 Fibre Optic FO connections Rx Tx Only optical fibres prepared according the regulat...

Page 24: ... Do not make any changes at the device Check whether the operation data comply with the values on the rating plate Not change any DIP switch at the device before reading this manual Connect FO cable to FO receiver Rx and FO transmitter Tx with the help of ST plugs Be carefull when connecting the FO plugs and avoid any dust at the FO connections Connect to RS485 terminals and screw them for permane...

Page 25: ...nr L2 Anr L3 Anr Er de Automat RUN ERROR LWL RS232 LWL LWL LWL LWL Mini Starcoupler 7XV5450 SIEMENS RUN ERROR Anr L1 Anr L2 L2 40 2 1 A Ma x4 50 1A L3 40 2 1 A Ma x4 50 1A SIPROTEC SIEMENS L1 402 1A Max450 1A L2 402 1A Max450 1A L3 402 1A Max450 1A E 00 0A Anr L1 Anr L2 Anr L3 Anr Er de Automat RUN ERROR SIEMENS RUN ERROR Anr L1 Anr L2 FO RS485 Converter 7XV5650 FO RS485 Converter 7XV5651 DIGSI Mo...

Page 26: ... L2 40 2 1 A Ma x4 50 1A L3 40 2 1 A Ma x4 50 1A SIPROTEC SIEMENS L1 402 1A Max450 1A L2 402 1A Max450 1A L3 402 1A Max450 1A E 00 0A Anr L1 Anr L2 Anr L3 Anr Erde Automat RUN ERROR FO RS485 Converter 7XV5650 SIEMENS RUN ERROR Anr L1 Anr L2 L2 40 2 1 A Ma x4 50 1A L3 40 2 1 A Ma x4 50 1A 7XV5101 7XV5101 DIGSIModem Substation modem 7XV58xx Modem Office modem 7XV58xx Public network Modem cable 7XV58...

Page 27: ...ates zur Angleichung der Rechtsvorschriften der Mitgliedstaaten betreffend elektrische Betriebsmittel zur Verwendung innerhalb bestimmter Span nungsgrenzen geändert durch 93 68 EWG Council Directive on the approximation of the laws of the Member States related to electrical equipment designed for use within certain voltage limits amended by 93 68 EEC Die Konformität mit den Richtlinien wird nachge...

Page 28: ...bution Power Automation Depart PTD PA 13 Postfach 4806 D 90026 Nürnberg Telefax 49 911 433 8301 Further informations regarding our products in the INTERNET under http www SIPROTEC com or please visit our Download Area which is part of our WEB site where also the latest version of this manual is available as a PDF file Printed in Germany ...