Figure 3 Switch positions (example)
Matching the frequency of polarity reversal:
The preset value of 1.5 Hz is an experimental value and usually the user does not have to
change it.
The value must be lowered in case of larger rotor earth capacitances or if the excitation
system is equipped with capacitors towards earth. Read out the operational measured value
R
earth
of the protective device. If the value of the rotor earth capacitance is too low supposed
there is no fault, the frequency of polarity reversal is to be reduced. As an alternative, the
fault recording function of the device can be applied. When executing fault recording select
its instantaneous value acquisition mode. Furthermore, a test record must be initiated via the
operating program with the generator not being excited. To ensure proper functioning the
protection system needs a signal, which is charge exchange free for approx. 100 ms, each
time polarity reversal is carried out (see Figure 4).
Figure 4 Charge exchange process with the generator not being excited
For smaller rotor-earth-capacities the user may raise the frequency of polarity. In a next step
please check the measured results with the machine being excited.
Front view of switch S1 and S2:
Position „230 V”
Position „0,5 Hz”
Factory set:
Position „115 V”
Position „1,5 Hz”
U
Mess
(t)
approx. 100 ms
approx. 100 ms
Summary of Contents for 7XT71 Series
Page 2: ...English Русский 7XT7100 0 A00 DD 2 C53000 B119U C128 1 ...
Page 22: ...English 7XT7100 0 A00 DD 22 C53000 B119U C128 1 ...
Page 44: ...Русский 7XT7100 0 A00 DD 44 C53000 B119U C128 1 ...
Page 45: ...7XT7100 0 A00 DD C53000 B119U C128 1 45 ...
Page 46: ...7XT7100 0 A00 DD 46 C53000 B119U C128 1 ...