80
9
&*&
2104 f STAGE 2
Pick-up value for stage f2
min. 40.00
Hz
max. 65.00
©©©©
2105 MEA.REP.f2
Number of meas. repetitions stage f2
min. 2
max. 10000
©©©©
2106 f STAGE 3
Pick-up value for stage f3
min. 40.00
Hz
max. 65.00
©©©©
2107 MEA.REP.f3
Number of meas. repetitions stage f3
min. 2
max. 10000
©©©©
2108 f STAGE 4
Pick-up value for stage f4
min. 40.00
Hz
max. 65.00
©©©©
2109 MEA.REP.f4
Number of meas. repetitions stage f4
min. 2
max. 10000
©©©©
2110 BLOCK. U<
Minimum operating voltage for frequency prot.
min. 40
V
max. 100
©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
2900 MEAS.VALUE SUPERVISION
2901 M.V.SUPERV
State of measured values supervision
OFF
[ ] off
ON
[ ] on
2902 SYM.Uthres
Symmetry threshold for voltage monitoring
min. 10
V
max. 100
©©©©
2903 SYM.Fact.U
Symmetry factor for voltage monitoring
min. 0.58
max. 0.95
©©©©
2904 SUM.Uthres
Voltage threshold for voltage summation
min. 10
V
max. 200
©©©©
2905 SUM.Fact.U
Factor for voltage summation monitoring
min. 0.60
max. 0.95
©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
3000 EXTERNAL TRIP FUNCTION 1
3001 EXT.TRIP 1
State of external trip function 1
OFF
[ ] off
ON
[ ] on
BLOCK TRIP REL
[ ] Block trip relay